PID Control Specifications

ItemSpecificationNote
Proportional Gain (Kp)1 ~ 30,0001 ~ 6,553,500
Integral Gain (Ki)0 ~ 30,000
(0.0s ~ 3,000.0s)
No Integral Operation: 0
Derivative Gain (Kd)0 ~ 30,000
(0.0s ~ 3,000.0s)
No Derivative Operation: 0
Sampling Interval (Ts)1 ~ 6,000
(0.01s ~ 60.00s)
Range of Set Value (SV)0 ~ 16,000
Range of Process Value (PV)0 ~ 16,000
Range of Manipulated Output Value (MV)0 ~ 16,000
Range of Manually Manipulated Value (MVMAN)0 ~ 16,000
PID Control Loop32 or 64 Loops
Control OperationForward Operation
Reverse Operation
Type of OperationDifferentiates Measured Values
  • Proportional gain can maximize its setting range up to 100 times by using the function selection flag of the PIDCAL instruction.
    • By enabling this function, the range value of Kp can be expanded from 1 ~ 66,553,500.