In this section
Browse the pages in this section for detailed information on each topic.
IO-SA0400 Internal I/O Table InputName of SignalOutputName of SignalXn.0RTD Module ReadyYn.0ReservedXn.1RTD conversion completion flagYn.1ReservedXn.2Set value saving completion flagYn.2Requesting to save set valueXn.3ReservedYn.3ReservedXn.4ReservedYn.4ReservedXn.5ReservedYn.5ReservedXn.6ReservedYn.6ReservedXn.7ReservedYn.7ReservedXn.8ReservedYn.8ReservedXn.9ReservedYn.9ReservedXn.AReservedYn.AReservedXn.BReservedYn.BReservedXn.CReservedYn.CReservedXn.DReservedYn.DReservedXn.EReservedYn.ERequesting circuit calibrationXn.FRTD Module Error FlagYn.FRequesting to Clear Error Flag Input Signal Data RegisterSignal NameDescriptionXn.0RTD Module ReadyThis signal is turned ON at the time RTD conversion is completely ready (CPU power is ON).Xn.1RTD Conversion…
Memory Address(Hexadecimal)Memory Address(Decimal)DetailsReadWrite00H0RTD conversion Enable/Disable✓✓01H1Channel 1 Temperature detection value (°C)✓-02H2Channel 2 Temperature detection value (°C)✓-03H3Channel 3 Temperature detection value (°C)✓-04H4Channel 4 Temperature detection value (°C)✓-05H5Reserved–06H6Reserved–07H7Reserved–08H8Reserved–09H9Designate RTD type✓✓0AH10Digital output setting 1✓✓0BH11Channel 1 Temperature detection value (°F)✓-0CH12Channel 2 Temperature detection value (°F)✓-0DH13Channel 3 Temperature detection value (°F)✓-0EH14Channel 4 Temperature detection value (°F)✓-0FH15Reserved–10H16Reserved–11H17Reserved–12H18Reserved–13H19Information for operation channel✓-14H20Designate RTD type✓✓15H21Channel…
IO-SA0400 Troubleshooting RUN LED Light Blinking (0.3 seconds) If the RUN LED light is blinking every 0.3 seconds, check the error code in the module status window of MapleLogic. The error code is displayed as 0, 1, 2, 3, or 10. RUN LED Light Blinking (0.5 seconds) & Temperature Not Changing The RTD module is…
IO-SA0400 Wiring Guide ChannelA TerminalB Terminalb TerminalChannel 1Terminal 1Terminal 2Terminal 3Channel 2Terminal 4Terminal 5Terminal 6Channel 3Terminal 7Terminal 8Terminal 9Channel 4Terminal 10Terminal 11Terminal 12 The 24V External is connected on the bottom of the module.
RTD Module Features The IO-SA0400 measures the input from a resistor and converts it into a 14-bit digital temperature (°C/°F) value. The RTD module converts temperature from the following resistor types into a 1-digit number after the decimal point. It outputs a digital value in the range 0 ~ 16,000. Platinum100 (PT100) Platinum1000 (PT1000) Japanese Platinum100…
Resistance Temperature Detector (RTD) Navigate to Online → Special Module Setup → RTD Module or click on the RTD module within the Card Properties. Applied Modules IO-SA0400 RTD Module Step 1: Hold CTRL to configure all channels at once. Step 2: Click Setup to configure the RTD type, digital value range, digital filter constant, or average time. RTD Type: Platinum 100 (PT100) Japenese Platinum 100 (JPT100) Platinum 1,000 (PT1000) Nickel…
Consecutively Changing An analog value is a consecutively changing value, such as voltage, current, temperature, velocity, pressure, and flow rate. For example, a temperature value is consecutively changing with time. However, as the changing temperature value is directly input into the PLC, its equivalent analog amount of DC voltage (0V ~ +10V) or DC current…
RTD Module General Specifications SpecificationDescriptionStandardsOperating Temperature-10°C ~ 65°C14°F ~ 149°F-Storage Temperature-25°C ~ 80°C-13°F ~ 176°F-Operating Humidity5% ~ 95% RH, Non-condensing-Storage Humidity5% ~ 95% RH, Non-condensing- Intermittent Vibration FrequencyAccelerationAmplitudeTimes5Hz ≤ f < 9Hz-3.5mm10 times in X, Y, and Z9Hz ≤ f ≤ 150Hz9.8m/s2 (1G)-10 times in X, Y, and Z Standard IEC 61131-2 Continuous Vibration FrequencyAccelerationAmplitudeTimes5Hz…
IO-SA0400 Functions RTD Conversion Enable/Disable For each channel, users can set RTD conversion to be enabled or disabled. For unused channels, users can make the conversion time short by setting them to disabled. Temperature Detection Value The temperature detection value saves a converted Celsius and Fahrenheit value into memory. This is down to the first…