In this section
Browse the pages in this section for detailed information on each topic.
Analog-to-Digital (AD) Conversion Method The IO-SA0400Y and IO-SA0800Y analog modules use input analog-to-digital conversion. Sampling Processing Sampling processing converts analog input signals to digital signals through general analog-to-digital conversion processing. The digital conversion value is saved to the buffer memory of the each module. The required time for sampling processing is a 2.1ms interval. This is…
IO-SA0400Y Internal I/O Table InputName of SignalOutputName of SignalXn.0AD Module ReadyYn.0Not UsedXn.1ReservedYn.1Not UsedXn.2Flag indicating the operation condition set upYn.2Requesting to set up an operation conditionXn.3ReservedYn.3ReservedXn.4ReservedYn.4ReservedXn.5ReservedYn.5ReservedXn.6ReservedYn.6ReservedXn.7Channel 1 Maximum Alarm ValueYn.7ReservedXn.8Channel 2 Maximum Alarm ValueYn.8ReservedXn.9Channel 3 Maximum Alarm ValueYn.9ReservedXn.AChannel 4 Maximum Alarm ValueYn.AReservedXn.BChannel 1 Minimum Alarm ValueYn.BReservedXn.CChannel 2 Minimum Alarm ValueYn.CReservedXn.DChannel 3 Minimum Alarm ValueYn.DReservedXn.EChannel 4 Minimum…
IO-SA0400Y Buffer Memory Memory Address(Hexadecimal)Memory Address(Decimal)DetailsDefaultReadWrite00H0Channel 1 Digital conversion value-✓-01H1Channel 2 Digital conversion value-✓-02H2Channel 3 Digital conversion value-✓-03H3Channel 4 Digital conversion value-✓-04H4Channel 1 Precise value-✓-05H5Channel 2 Precise value-✓-06H6Channel 3 Precise value-✓-07H7Channel 4 Precise value-✓-08H8Channel 1 Percentile value-✓-09H9Channel 2 Percentile value-✓-0AH10Channel 3 Percentile value-✓-0BH11Channel 4 Percentile value-✓-0CH12Channel 1 Setup input signal range0✓✓0DH13Channel 2 Setup input signal…
IO-SA0800Y Analog Buffer Memory Memory Address(Hexadecimal)Memory Address(Decimal)DetailsDefaultReadWrite00H0Channel 1 Digital conversion value-✓-01H1Channel 2 Digital conversion value-✓-02H2Channel 3 Digital conversion value-✓-03H3Channel 4 Digital conversion value-✓-04H4Channel 5 Digital conversion value-✓-05H5Channel 6 Digital conversion value-✓-06H6Channel 7 Digital conversion value-✓-07H7Channel 8 Digital conversion value-✓-08H8Channel 1 Precise value-✓-09H9Channel 2 Precise value-✓-0AH10Channel 3 Precise value-✓-0BH11Channel 4 Precise value-✓-0CH12Channel 5 Precise value-✓-0DH13Channel 6…
IO-SA0400Y Voltage Input Wiring ChannelPositive (+) TerminalNegative (-) TerminalChannel 1Terminal 1Terminal 3Channel 2Terminal 4Terminal 6Channel 3Terminal 7Terminal 9Channel 4Terminal 10Terminal 12 The 24V External is connected on the bottom of the module. Current Input Wiring ChannelPositive (+) TerminalNegative (-) TerminalAdditional ConnectionChannel 1Terminal 1Terminal 3Connect 1-2Channel 2Terminal 4Terminal 6Connect 4-5Channel 3Terminal 7Terminal 9Connect 7-8Channel 4Terminal 10Terminal…
Analog to Digital (AD) Navigate to Online → Special Module Setup → AD Module or click on the AD module within the Card Properties. Applied Modules IO-SA0400Y IO-SA0800Y AD Module Details Step 1: Hold CTRL to configure all channels at once. Step 2: Click Setup to choose the signal type, digital range, filter constant, sampling time, average window size,…
The IO-SA0400Y and IO-SA0800Y expansion modules support the following features: Input signals can be configured for current or voltage signals. Multiple analog value ranges for current or voltage. Current; 0mA ~ 20mA 4mA ~ 20mA (default) Voltage: -10V ~ 10V 0V ~ 10V 0V ~ 5V 1V ~ 5V Multiple digital value ranges for conversion:…
Analog Input Module Specifications SpecificationDescriptionStandardsOperating Temperature-10°C ~ 65°C14°F ~ 149°F-Storage Temperature-25°C ~ 80°C-13°F ~ 176°F-Operating Humidity5% ~ 95% RH, Non-condensing-Storage Humidity5% ~ 95% RH, Non-condensing- Intermittent Vibration FrequencyAccelerationAmplitudeTimes5Hz ≤ f < 9Hz-3.5mm10 times in X, Y, and Z9Hz ≤ f ≤ 150Hz9.8m/s2 (1G)-10 times in X, Y, and Z Standard IEC 61131-2 Continuous Vibration FrequencyAccelerationAmplitudeTimes5Hz…
IO-SA0400Y & IO-SA0800Y Voltage Conversion NumberAnalog Input VoltageOffsetGainDigital OutputMaximum Resolution1+1V ~ +5V+1V+5V0 ~ 16,000-8,000 ~ 8,000312.5mV2+0V ~ +5V+0V+5V0 ~ 16,000-8,000 ~ 8,000250mV3+0V ~ +10V+0V+10V0 ~ 16,000-8,000 ~ 8,000625mV4-10V ~ +10V-10V+10V0 ~ 16,000-8,000 ~ 8,0001,250mV IO-SA0400Y & IO-SA0800Y Current Conversion NumberAnalog Input CurrentOffsetGainDigital OutputMaximum Resolution10mA ~ 20mA0mA20mA0 ~ 16,000-8,000 ~ 8,0001.25nA24mA ~ 20mA4mA20mA0 ~ 16,000-8,000 ~…