PWM Module General Specifications

SpecificationDescriptionStandards
Operating Temperature-10°C ~ 65°C
14°F ~ 149°F
Storage Temperature-25°C ~ 80°C
-13°F ~ 176°F
Operating Humidity5% ~ 95% RH, Non-condensing
Storage Humidity5% ~ 95% RH, Non-condensing

Intermittent Vibration

FrequencyAccelerationAmplitudeTimes
5Hz ≤ f < 9Hz3.5mm10 times in X, Y, and Z
9Hz ≤ f ≤ 150Hz9.8m/s2 (1G)10 times in X, Y, and Z

Standard IEC 61131-2

Continuous Vibration

FrequencyAccelerationAmplitudeTimes
5Hz ≤ f < 9Hz1.75mm10 times in X, Y, and Z
9Hz ≤ f ≤ 150Hz4.9m/s2 (0.5G)10 times in X, Y, and Z

Standard IEC 61131-2

Shocks

DescriptionStandard
Maximum Shock Acceleration: 147m/s2 (15G)
Time: 11ms
Pulse Wave: Sine Half-Wave (3 times in X, Y, Z)
IEC 61131-2

Noise

SpecificationDescriptionStandard
Square Wave Impulse Noise±2kV
Electrostatic DischargeVoltage: 4kV (contact) 8kV (air)IEC 61131-2
IEC 61000-4-2
Radiated Electromagnetic Field80MHz ~ 1,000MHz
10V/m
IEC 61131-2
IEC61000-4-3

Fast Transient Burst Noise (Voltage)

Fast Transient Burst Noise (Voltage) TypeDescriptionStandard
CPU Power2kVIEC 61131-2
IEC 61000-4-4
Digital/Analog I/O (AC)2kVIEC 61131-2
IEC 61000-4-4
Digital/Analog I/O (DC)1kVIEC 61131-2
IEC 61000-4-4
Communication1kVIEC 61131-2
IEC 61000-4-4

Environment

No corrosive gas
No dust

Altitude

2,000m or less

Pollution

Pollution Degree 2 or less

Cooling

Natural air cooling

PWM Module Physical Specifications

SpecificationIO-SD0032PPWM
Weight66g
Dimensions20mm x 63mm x 90mm
0.787in x 2.480in x 3.543in
Rated I/O VoltageDC 12V-24V
Response Time≤ 1ms
Operation IndicatorLED is ON when input is ON
Insulation MethodPhotocoupler
Output MethodSource
Digital Outputs32 Points
(Including PWM Output)
PWM Outputs12 Points
(Included in digital outputs)

PWM Module Performance Specifications

SpecificationIO-SD0032PPWM
Frequency Range
Duty Cycle Guarantee
1 ~ 4,000pps
Maximum Output Frequency65,000pps
Duty Cycle Resolution0% ~ 100%
Resolution 1/1,000
RAMP ControlFrequency RAMP
DUTY ratio RAMP control