Instruction Parameters

Supported PLC Series

PLC-AESPLC-FBPLC-ES

Supported Data Registers

MXYKLFTCSZRQD@DConstant
n1
n2
S
n3

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1
CarryF11.2

Number of Steps

Steps
5

Operands

OperandDescription
n1The first operand.
Entries are Hexadecimal WORD data registers or constants.
This is the base and slot number of the expansion module to write to.

This number depends on the amount of expansion modules the chassis contains.
n2The second operand.
Entries are WORD data registers or constants.
This is the address of buffer memory where the data is written.

The value range depends on the buffer memory to write to.
SThe third operand.
Entries are WORD data registers or constants.
This is the data to write to the buffer memory of the expansion module.
n3The fourth operand.
Entries are WORD data registers or constants.
This is the amount of WORD data to write.

The value range is 0 ~ 255.

Assignment Example

The following example shows how to assign values to n1 and Base/Slot.

n1

Base NumberSlot Number
H0A0B
Hexadecimal2 Digits in Hexadecimal2 Digits in Hexadecimal

CM1 vs CM3

The base number and slot number depend on the chassis type. Since the CM3 chassis can only go up to 11 or 15 expansion modules, the base number is always 00.

Base/Slot (CM1)

Base NumberSlotExample
Local BaseSlot Number 5H0005 or 5
1st ExpansionSlot Number 3H0103
10th ExpansionSlot Number 7H0A07
14th ExpansionSlot Number 12H0E0C
16th ExpansionSlot Number 10H100A

Module/Slot (CM3)

ModuleSlotExample
CPUSlot 0H0000 or 0
1st ExpansionSlot 1H0001 or 1
5th ExpansionSlot 5H0005 or 5
10th ExpansionSlot 10H000A
15th ExpansionSlot 15H000F

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type. F11.0 turns ON when access to the expansion module fails. F11.0 turns ON when the base and slot number assigned to n1 is not an expansion module. F11.0 turns ON when the number of data in n3 exceeds the range of the data register assigned to S.

Execution Condition

It is recommended that the TO instruction be used with a pulse contact as an execution condition, or use the TOP instruction.

Ladder Diagram Examples

TO

The TO instruction writes n3 number of WORD data, S, to the buffer memory location, n2, on the expansion module, n1.

The TO instruction writes n3 number of WORD data, S, to the buffer memory location, n2, on the expansion module, n1.

When the contact, M0.0, is ON (1), 1 WORD value of the data register, D0, is written to buffer memory 26 on the expansion module at slot H0003.

When the contact, M0.0, is ON (1), 1 WORD value of the data register, D0, is written to buffer memory 26 on the expansion module at slot H0003.

In this example, 2,281 is written to the digital output value buffer memory of the CM3-SP04EAA expansion module at slot 3.

In this example, 2,281 is written to the digital output value buffer memory of the CM3-SP04EAA expansion module at slot 3.

Memory Monitor

Memory Monitor for MapleLogic TO/TOP instruction.

TOP

The TOP one-shot instruction writes n3 number of WORD data, S, to the buffer memory location, n2, on the expansion module, n1.

The TOP one-shot instruction writes n3 number of WORD data, S, to the buffer memory location, n2, on the expansion module, n1. Every time this instruction executes, it energizes the output only once.

When the contact, M2.0, is ON (1), 1 WORD value of the data register, D10, is written to buffer memory 42 on the expansion module at slot H0004.

When the contact, M2.0, is ON (1), 1 WORD value of the data register, D10, is written to buffer memory 42 on the expansion module at slot H0004.

In this example, 320 is written to the maximum temperature value buffer memory (channel 2) of the CM3-SP04ERO expansion module at slot 4.

In this example, 320 is written to the maximum temperature value buffer memory (channel 2) of the CM3-SP04ERO expansion module at slot 4.

Memory Monitor

Memory Monitor for MapleLogic TO/TOP instruction.