IO-SD0032PPWM RAMP Control

  • The output control of the IO-SD0032PPWM is available from 1 ~ 4,000pps.
  • RAMP is supported when the frequency value is changed.
    • Please refer to the RAMP instruction.
  • The frequency RAMP feature changes according to the frequency RAMP control time.
    • If the set time is 0, the frequency RAMP changes immediately.
  • The setting value for frequency can be changed during the RAMP operation.
    • However, changing the frequency RAMP control time can only be applied AFTER changing the frequency value.
PWM Parameters Frequency RAMP Control Time in MapleLogic
  • The IO-SD0032PPWM’s output DUTY cycle ratio can be controlled from 0% ~ 100%.
    • Please refer to the DUTY instruction.
  • There is support for the RAMP when DUTY cycle ratio changes feature.
  • The DUTY cycle RAMP function changes according to the frequency RAMP control time.
    • It instantly changes if the DUTY cycle RAMP time is set to 0.

  • If the DUTY RAMP control time is changed during the RAMP operation, the change will be applied in the NEXT operation.
PWM Parameters DUTY Cycle RAMP Control in MapleLogic
  • There are a maximum of 12 channels available for high-speed pulse-width modulation output that supports the RAMP feature.
    • Frequency RAMP and DUTY cycle RAMP operate individually.