Instruction Parameters

Supported PLC Series

PLC-AESPLC-FBPLC-ES

Supported Data Registers

MXYKLFTCSZRQD@DConstant
n1
n2
D

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1
CarryF11.2

Number of Steps

Steps
4

Operands

OperandDescription
n1The first operand.
Entries are WORD data registers or constants.
This is the number of scans that the user clock is ON.

The value range is 1 ~ 32,767.
n2The second operand.
Entries are WORD data registers or constants.
This is the number of scans that the user clock is OFF.

The value range is 1 ~ 32,767.
DThe third operand.
Entries are only BOOL data registers.
This is the address of the user clock.

The data register range is F10.0 ~ F10.7.

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type.

Instruction Behavior

The DUTY instruction behaves as follows:

  • Once energized, the assigned user clock turns ON and OFF continuously.
    • This is true even if the execution condition is OFF.
  • Only positive numbers can be assigned to n1 and n2.
    • The error flag, F11.0, will be ON if either value is negative.
  • Only the BOOL data registers, F10.0 ~ F10.7, can be assigned to the data register, D.
  • If the value assigned to either n1 or n2 changes while the execution condition is ON, the change is immediately applied to the user clock assigned to the data register, D.