In this section
Browse the pages in this section for detailed information on each topic.
Digital-to-Analog (DA) Navigate to Online → Special Module Setup → DA Module or click on the DA module within the Card Properties. Applied Modules IO-SA0004C IO-SA0004V DA Module Details Step 1: Hold CTRL to configure all channels at once. Step 2: Click Setup to enable/disable the module, or configure the digital value range, STOP mode output, or output signal. Digital Value Range: 0 ~ 16,000 -8,000 ~ 8,000 0 ~ 10,000…
The IO-SA0004C and IO-SA0004V expansion modules support the following features Multiple analog value ranges for current or voltage: IO-SA0004C (Current) 4mA ~ 20mA IO-SA0004V (Voltage) -10V ~ 10V 0V ~ 10V Multiple digital value ranges for conversion -8,000 ~ 8,000 0 ~ 16,000 Ability to output an offset value Used through the Hold/Clear function. LED indicator to…
Analog Output Module Specifications SpecificationDescriptionStandardsOperating Temperature-10°C ~ 65°C14°F ~ 149°F-Storage Temperature-25°C ~ 80°C-13°F ~ 176°F-Operating Humidity5% ~ 95% RH, Non-condensing-Storage Humidity5% ~ 95% RH, Non-condensing- Intermittent Vibration FrequencyAccelerationAmplitudeTimes5Hz ≤ f < 9Hz-3.5mm10 times in X, Y, and Z9Hz ≤ f ≤ 150Hz9.8m/s2 (1G)-10 times in X, Y, and Z Standard IEC 61131-2 Continuous Vibration FrequencyAccelerationAmplitudeTimes5Hz…
IO-SA0004C and IO-SA0004V Internal I/O Table InputName of SignalOutputName of SignalXn.0DA Module ReadyYn.0ReservedXn.1ReservedYn.1ReservedXn.2Flag indicating the operation condition set upYn.2Requesting to set up an operation conditionXn.3Channel 1 Output Enable (Status)Yn.3Channel 1 Output Enable (Control Command)Xn.4Channel 2 Output Enable (Status)Yn.4Channel 2 Output Enable (Control Command)Xn.5Channel 3 Output Enable (Status)Yn.5Channel 3 Output Enable (Control Command)Xn.6Channel 4 Output Enable…
To write to buffer memory, use the TO instruction To read from buffer memory, use the FROM instruction. Please refer to the table below for writing to and reading from buffer memory. Memory Address(Hexadecimal)Memory Address(Decimal)DetailsDefaultReadWrite00H0DA conversion Enable/Disable setup0✓✓01H1Channel 1 Digital output value0✓✓02H2Channel 2 Digital output value0✓✓03H3Channel 3 Digital output value0✓✓04H4Channel 4 Digital output value0✓✓05H5Channel 1…
IO-SA0004C Current Wiring ChannelPositive (+) TerminalNegative (-) TerminalAdditional ConnectionsChannel 1Terminal 1Terminal 2-Channel 2Terminal 3Terminal 4-Channel 3Terminal 5Terminal 6-Channel 4Terminal 7Terminal 8- The 24V External is connected on the bottom of the module. IO-SA0004V Voltage Wiring ChannelPositive (+) TerminalNegative (-) TerminalAdditional ConnectionsChannel 1Terminal 1Terminal 2-Channel 2Terminal 3Terminal 4-Channel 3Terminal 5Terminal 6-Channel 4Terminal 7Terminal 8- The 24V…
Error CodeDescription1The set digital value is out of the maximum range, 16,191 or 8,191.2The set digital value is out of the minimum range, -192 or -8,192.40An offset value is greater than a gain value.41An offset and gain value are calibrated, or plural channels are set up at the same time.42A calibrated digital value is out of range when calibrating the offset…