Specifications
Functional
Type | Thermocouple |
Digital Conversion | Digitally converted value: 0–16000 (-8000–8000)/- 192–16191 (-8192–8191); Converted temperature value: Range of measured temperature (one digit after the decimal point * 10) |
Wire Disconnection Detection | Each channel |
Number of Input Channels | 4 |
Max Conversion Rate | 50 ms/4 Channels |
Insulation Type | Photocoupler between input terminal and PLC power |
Accuracy | ±[(Full Scale) x 0.3% + 1°C (RJC Error)] |
Display
Contrast Ratio | 800 |
Electrical
Current Consumption +3.3V | 40 mA |
Current Consumption +24V | 10 mA |
Mechanical
Dimensions WxHxD | 90 x 20 x 60 mm (3.5 x 0.8 x 2.4 in) |
Weight | 153 g (0.34 lb) |
Shock | 15G |
Vibration | 0.5G - Continuous, 1G - Discontinuous |
Square Wave Impulse Noise | ±2 kV |
ESD Immunity | ±4 kV - Contact Discharges, ±8 kV - Air Discharges |
Surge Transient Immunity | 2 kV - CPU, Power; 2 kV - Digital I/O (VAC); 1 kV - Digital I/O (VDC); 1 kV - Communication |
Accessories
Customers who bought this product also bought:
Available Software
Documentation & Resources
Documents
Manuals
Certifications
Need Additional Support?
Maple Systems
808 134th St. SW, Suite 120
Everett, WA 98204
Phone: 425.745.3229
Fax: 425.745.3429
Email: sales@maplesystems.com
Business Hours:
Monday – Friday 6:00am – 4:30pm (PST)
What's Included
When you order the IO-SA0400T the following items are included in the box:
- IO-SA0400T
- Product Manual