Instruction Parameters
Supported PLC Series
| PLC-AES | PLC-FB | PLC-ES |
|---|---|---|
| ✓ | ✓ | ✓ |
Supported Data Registers
| M | X | Y | K | L | F | T | C | S | Z | R | Q | D | @D | Constant | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| S1 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | – | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
| S2 | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | – | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
| D | ✓ | – | ✓ | ✓ | ✓ | – | ✓ | ✓ | – | ✓ | ✓ | ✓ | ✓ | ✓ | – |
Supported Flags
| Flag | Bit | Support |
|---|---|---|
| Error | F11.0 | ✓ |
| Zero | F11.1 | ✓ |
| Carry | F11.2 | – |
Number of Steps
| Steps |
|---|
| 4 |
Operands
| Operand | Description |
|---|---|
| S1 | The first operand. Entries are DWORD data registers or constants. The signed value range is -2,147,483,648 ~ 2,147,483,647 (232). The unsigned value range is 0 ~ 4,294,967,295 (232-1). The Hexadecimal value range is H00000000 ~ HFFFFFFFF. |
| S2 | The second operand. Entries are DWORD data registers or constants. The signed value range is -2,147,483,648 ~ 2,147,483,647 (232). The unsigned value range is 0 ~ 4,294,967,295 (232-1). The Hexadecimal value range is H00000000 ~ HFFFFFFFF. |
| D | The third operand. Entries are only DWORD data registers. This is where the result of a logical S1 XOR S2 is saved. |
Notice
Error Flag (F11.0) Notice
The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type. F11.0 turns ON when the value of the data for a logical XOR exceeds the data register assigned to S1 or S2.
Logical Operation
The DXOR and DXORP instructions perform a logical XOR on each bit of S1 and S2.

Ladder Diagram Examples
DXOR

The DXOR instruction performs a logical XOR on the DWORD value, S1, and the DWORD value, S2, and saves the result in an assigned DWORD data register, D.

When the contact, M5.0, is powered ON (1), a logical XOR operation is performed on the DWORD data registers, D5 and D8. The result of the logical XOR operation is saved in the DWORD data register, D11.

Memory Monitor


DXORP

The DXORP one-shot instruction performs a logical XOR on the DWORD value, S1, and the DWORD value, S2, and saves the result in an assigned DWORD data register, D. Every time this instruction energizes, it executes only once.

When the contact, M5.1, is powered ON (1), a logical XOR operation is performed on the DWORD data registers, D15 and D18. The result of the logical XOR operation is saved in the DWORD data register, D21.

Memory Monitor