Instruction Parameters

Supported PLC Series

PLC-AESPLC-FBPLC-ES

Supported Data Registers

MXYKLFTCSZRQD@DConstant
S1
S2
D

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1
CarryF11.2

Number of Steps

Steps
4

Operands

OperandDescription
S1The first operand.
Entries are DWORD data registers or constants.

The signed value range is -2,147,483,648 ~ 2,147,483,647 (232).
The unsigned value range is 0 ~ 4,294,967,295 (232-1).
The Hexadecimal value range is H00000000 ~ HFFFFFFFF.
S2The second operand.
Entries are DWORD data registers or constants.

The signed value range is -2,147,483,648 ~ 2,147,483,647 (232).
The unsigned value range is 0 ~ 4,294,967,295 (232-1).
The Hexadecimal value range is H00000000 ~ HFFFFFFFF.
DThe third operand.
Entries are only DWORD data registers.
This is where the result of a logical S1 XNOR S2 is saved.

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type. F11.0 turns ON when the value of the data for a logical XNOR exceeds the data register assigned to S1 or S2.

Logical Operation

The DXNR and DXNRP instructions perform a logical XNOR on each bit of S1 and S2.

Notice for MapleLogic DXNR/DXNRP instruction.

Ladder Diagram Examples

DXNR

The DXNR instruction performs a logical XNOR on the DWORD value, S1, and the DWORD value, S2, and saves the result in an assigned DWORD data register,

The DXNR instruction performs a logical XNOR on the DWORD value, S1, and the DWORD value, S2, and saves the result in an assigned DWORD data register, D.

When the contact, M0.2, is powered ON (1), a logical XNOR operation is performed on the DWORD data registers, D30 and D33.

When the contact, M0.2, is powered ON (1), a logical XNOR operation is performed on the DWORD data registers, D30 and D33. The result of the logical XNOR operation is saved in the DWORD data register, D36.

Ladder Diagram Example for MapleLogic DXNR/DXNRP instruction.

Memory Monitor

Memory Monitor for MapleLogic DXNR/DXNRP instruction.
Memory Monitor for MapleLogic DXNR/DXNRP instruction.

DXNRP

The DXNRP one-shot instruction performs a logical XNOR on the DWORD value, S1, and the DWORD value, S2, and saves the result in an assigned DWORD data

The DXNRP one-shot instruction performs a logical XNOR on the DWORD value, S1, and the DWORD value, S2, and saves the result in an assigned DWORD data register, D. Every time this instruction energizes, it executes only once.

When the contact, M0.4, is powered ON (1), a logical XNOR operation is performed on the DWORD data registers, D40 and D43.

When the contact, M0.4, is powered ON (1), a logical XNOR operation is performed on the DWORD data registers, D40 and D43. The result of the logical XNOR operation is saved in the DWORD data register, D46.

Ladder Diagram Example for MapleLogic DXNR/DXNRP instruction.

Memory Monitor

Memory Monitor for MapleLogic DXNR/DXNRP instruction.
Memory Monitor for MapleLogic DXNR/DXNRP instruction.