Instruction Parameters

Supported PLC Series

PLC-AESPLC-FBPLC-ES

Supported Data Registers

MXYKLFTCSZRQD@DConstant
S1
S2
D
n

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1
CarryF11.2

Number of Steps

Steps
5

Operands

OperandDescription
S1The first operand.
Entries are only WORD data registers.

The signed value range is for each data register -32,768 ~ 32,767 (216).
The unsigned value range for each data register is 0 ~ 65,535 (216-1).
The Hexadecimal value range for each data register is H0000 ~ HFFFF.
S2The second operand.
Entries are WORD data registers or constants.

The signed value range for each data register is -32,768 ~ 32,767 (216).
The unsigned value for each data register range is 0 ~ 65,535 (216-1).
The Hexadecimal value for each data register range is H0000 ~ HFFFF.
DThe third operand.
Entries are only WORD data registers.
This is where the result of a logical S1 AND S2 is saved.
nThe fourth operand.
Entries are WORD data registers or constants.
This is the amount of words for a logical S1 ~ Sn AND S2 ~ Sn.

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type. F11.0 turns ON when the value of the data for a logical AND exceeds the data register assigned to S1 or S2.

Logical Operation

The BKAND and BKANDP instructions will perform a logical AND on each bit of the data registers between S1 ~ Sn and S2 ~ Sn.

Notice for MapleLogic BKAND/BKANDP instruction.

Ladder Diagram Examples

BKAND

The BKAND instruction performs a logical AND on n number of WORD data registers starting at S1 and n number of data registers starting at S2 and saves

The BKAND instruction performs a logical AND on n number of WORD data registers starting at S1 and n number of data registers starting at S2 and saves the result in an assigned WORD data register, D.

When the contact, M6.0, is powered ON (1), logical AND operations are performed on 3 WORD data registers, D0, D1, and D2, with another 3 WORD data reg

When the contact, M6.0, is powered ON (1), logical AND operations are performed on 3 WORD data registers, D0, D1, and D2, with another 3 WORD data registers, D4, D5, and D6. The results of the logical AND operations are saved in 3 WORD data registers, D8, D9, and D10.

Ladder Diagram Example for MapleLogic BKAND/BKANDP instruction.

Memory Monitor

The below image shows the direct logical AND operations for each data register.

The below image shows the direct logical AND operations for each data register.

Memory Monitor for MapleLogic BKAND/BKANDP instruction.

BKANDP

The BKANDP one-shot instruction performs a logical AND on n number of WORD data registers starting at S1 and n number of data registers starting at S2

The BKANDP one-shot instruction performs a logical AND on n number of WORD data registers starting at S1 and n number of data registers starting at S2 and saves the result in an assigned WORD data register, D. Every time this instruction energizes, it executes only once.

When the contact, M7.0, is powered ON (1), logical AND operations are performed on 4 WORD data registers, D10, D11, D12, and D13, with another 4 WORD

When the contact, M7.0, is powered ON (1), logical AND operations are performed on 4 WORD data registers, D10, D11, D12, and D13, with another 4 WORD data registers, D15, D16, D17, and D18. The results of the logical AND operations are saved in 4 WORD data registers, D20, D21, D22, and D23.

Ladder Diagram Example for MapleLogic BKAND/BKANDP instruction.

Memory Monitor

The below image shows the direct logical AND operations for each data register.

The below image shows the direct logical AND operations for each data register.

Memory Monitor for MapleLogic BKAND/BKANDP instruction.