Comparison Uses

There are three types of comparison uses:

  • LDD (Ladder Diagram)
  • ANDD
  • ORD

The following compare instructions can be used as a:

  • DWORD standalone execution condition (LDD)
  • DWORD and execution condition (ANDD)
  • DWORD or execution condition (ORD)

Instruction Parameters

Supported PLC Series

PLC-AESPLC-FBPLC-ES

Supported Data Registers

MXYKLFTCSZRQD@DConstant
S1
S2

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1
CarryF11.2

Number of Steps

Steps
3

Operands

OperandDescription
S1The first operand.
Entries are signed DWORD data registers or constants.

The signed value range is -2,147,483,648 ~ 2,147,483,647 (232).
The Hexadecimal value range is H00000000 ~ HFFFFFFFF.

Only DWORD values will be compared.
Only signed or Hexadecimal values will be compared.
S2The second operand.
Entries are signed DWORD data registers or constants.

The signed value range is -2,147,483,648 ~ 2,147,483,647 (232).
The Hexadecimal value range is H00000000 ~ HFFFFFFFF.

Only DWORD values will be compared.
Only signed or Hexadecimal values will be compared.

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type.

Signed Overflow

DWORD data register entry behaves as follows:

  • If the value of S1 or S2 exceeds the smallest signed value -2,147,483,648, the value will be set to -2,147,483,648 with no warning.
  • If the value of S1 or S2 exceeds the largest signed value 2,147,483,647, the value will be set to 2,147,483,647 with no warning.

Ladder Diagram Examples

D>=

The D>= instruction compares a DWORD value, S1, to another DWORD value, S2, and executes if S1 is greater than or equal to S2.

LDD Execution Condition

When the result of the instruction execution of the expression D14 ≥ D16 (-457,913 ≥ 987,421) is FALSE, the coil, Y4.3, is deenergized.

When the result of the instruction execution of the expression D14D16 (-457,913987,421) is FALSE, the coil, Y4.3, is deenergized.

When the result of the instruction execution of the expression D14 ≥ D16 (13,556 ≥ 0) is TRUE, the coil, Y4.3, is energized.

When the result of the instruction execution of the expression D14D16 (13,5560) is TRUE, the coil, Y4.3, is energized.

Memory Monitor

Memory Monitor for MapleLogic GREATER/THAN/EQUAL/TO instruction.

ANDD Execution Condition

When the result of the instruction execution of the expression D18 ≥ D20 (-5,656,565 ≥ 1,211,212) is FALSE, and the contact, M0.0 is ON (1

When the result of the instruction execution of the expression D18D20 (-5,656,5651,211,212) is FALSE, and the contact, M0.0 is ON (1), the coil, Y4.4, is deenergized.

When the result of the instruction execution of the expression D18 ≥ D20 (5,656,565 ≥ 1,211,212) is TRUE, and the contact, M0.0 is ON (1),

When the result of the instruction execution of the expression D18D20 (5,656,5651,211,212) is TRUE, and the contact, M0.0 is ON (1), the coil, Y4.4, is energized.

Memory Monitor

Memory Monitor for MapleLogic GREATER/THAN/EQUAL/TO instruction.

ORD Execution Condition

When the result of the instruction execution of the expression D22 ≥ D24 (-98,765,432 ≥ -87,654,321) is FALSE, or the contact, M0.1 is ON

When the result of the instruction execution of the expression D22D24 (-98,765,432-87,654,321) is FALSE, or the contact, M0.1 is ON (1), the coil, Y4.5, is energized.

When the result of the instruction execution of the expression D22 ≥ D24 (-87,654,321 ≥ -87,654,321) is TRUE, and the contact, M0.1 is OFF

When the result of the instruction execution of the expression D22D24 (-87,654,321-87,654,321) is TRUE, and the contact, M0.1 is OFF (0), the coil, Y4.5, is energized.

Memory Monitor

Memory Monitor for MapleLogic GREATER/THAN/EQUAL/TO instruction.