The leader in industrial automation and control solutions

Instruction Parameters

Supported PLC Series

PLC-AESPLC-FBPLC-ES

Supported Data Registers

MXYKLFTCSZRQD@DConstant
S1
S2
D

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1
CarryF11.2

Number of Steps

Steps
4

Operands

OperandDescription
S1The first operand.
Entries are REAL data registers or constants.

The value range is 2-127 ~ 2128 (-1.7014118e+38 ~ 3.4028237e+38).
S2The second operand.
Entries are REAL data registers or constants.

The value range is 2-127 ~ 2128 (-1.7014118e+38 ~ 3.4028237e+38).
DThe third operand.
Entries are only REAL data registers.
This is where the product is saved.

Float Representation

MantissaExponentSign
Bit 0 ~ Bit 22Bit 23 ~ Bit 30Bit 31

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type. F11.0 turns ON when the value of the data for multiplying exceeds the data register assigned to S1 or S2.

Ladder Diagram Examples

EMUL

The EMUL instruction multiplies a REAL value, S1, to a REAL value, S2, and saves the product in an assigned REAL data register, D.

The EMUL instruction multiplies a REAL value, S1, to a REAL value, S2, and saves the product in an assigned REAL data register, D.

When M1.0 is powered ON, the REAL data register, D1, is multiplied to the REAL data register, D4, and the product is saved in the REAL data register,

When M1.0 is powered ON, the REAL data register, D1, is multiplied to the REAL data register, D4, and the product is saved in the REAL data register, D7.

Ladder Diagram Example for MapleLogic EMUL/EMULP instruction.

Memory Monitor

Memory Monitor for MapleLogic EMUL/EMULP instruction.

EMULP

The EMULP one-shot instruction multiplies a REAL value, S1, to a REAL value, S2, and saves the product in an assigned REAL data register, D.

The EMULP one-shot instruction multiplies a REAL value, S1, to a REAL value, S2, and saves the product in an assigned REAL data register, D. Every time this instruction executes, it energizes the output only once.

When M1.0 is powered ON, the REAL data register, D1, is multiplied to the REAL data register, D4, and the product is saved in the REAL data register,

When M1.0 is powered ON, the REAL data register, D1, is multiplied to the REAL data register, D4, and the product is saved in the REAL data register, D7.

Ladder Diagram Example for MapleLogic EMUL/EMULP instruction.

Memory Monitor

Memory Monitor for MapleLogic EMUL/EMULP instruction.