Instruction Parameters

Supported PLC Series

PLC-AESPLC-FBPLC-ES

Supported Data Registers

MXYKLFTCSZRQD@DConstant
t
v

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1
CarryF11.2

Number of Steps

Steps
3

Operands

OperandDescription
tThe first operand.
Entries are only timer data registers.
vThe second operand.
Entries are unsigned WORD data registers or constants.
This is the value the timer will count down from.

The unsigned value range is 0 ~ 65,535 (216-1).
The Hexadecimal value range is H0000 ~ HFFFF.

Signed value entries will be treated as unsigned values.

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by Z exceeds its range. The valid range of the data register Z is Z128 ~ Z1023 when using Function Block implementation.

Instruction Behavior

The TOFF instruction behaves as follows:

  • The data register T assigned to t is a BOOL data register.
    • TS and TC express the detailed value of the data register T assigned to t.
      • TC is a WORD data register used for the current time value of t.
      • TS is a WORD data register used for the time setting value of t.
        • The value of TS is equal to the value of v.
  • The value of TC changes as follows:
    • When the instruction is energized, the value of TC is equal to v.
    • When the instruction is deenergized, the value of TC decreases from the value equal to v.
      • The timer contact t is ON while TC decreases.
    • When TC decreases to 0, the timer contact t turns OFF.
    • If the instruction reenergizes while counting down, the value of TC is reset equal to v.
  • The actual time for the timer data register t is calculated as follows:
    • Actual Time = v × time unit (100ms or 10ms)
  • The timer contact assigned to t can be used as an A or B contact.
  • When the timer contact meets the RST instruction, the current value is 0 and the timer turns OFF.

Timer Length

Please refer to the PLC Parameter section for more information about 10ms and 100ms timers.

Ladder Diagram Examples

TOFF

The TOFF instruction starts from a WORD value, v, and counts down to 0. The time is saved in a timer data register, t.

The TOFF instruction starts from a WORD value, v, and counts down to 0. The time is saved in a timer data register, t.

When the contact M0.2 is powered ON, the value of the data register TC.2 is set to 150.

When the contact M0.2 is powered ON, the value of the data register TC.2 is set to 150.

While the value of the data register TC.2 is greater than 0, the timer contact T.2 is powered ON.

While the value of the data register TC.2 is greater than 0, the timer contact T.2 is powered ON. As a result, the coil Y2.0 is energized.

When the contact M0.2 is powered OFF, the data register TC.2 counts down to 0.

When the contact M0.2 is powered OFF, the data register TC.2 counts down to 0. The timer contact T.2 remains powered ON since the value of the data register TC.2 is greater than 0.

Once the value of the data register TC.2 is 0, the timer contact T.2 is powered OFF.

Once the value of the data register TC.2 is 0, the timer contact T.2 is powered OFF. As a result, the coil Y2.0 is deenergized.

Memory Monitor

This is the result of the data register TC.2 counting down to 0.

This is the result of the data register TC.2 counting down to 0.

This is the result of the timer contact T.2 once the value of TC.1 is 0.

This is the result of the timer contact T.2 once the value of TC.1 is 0.