CodeError NameDescriptionRange
0No ErrorPID is functioning without error.
1Error in Number of LoopsThe loop value is out of the range, 1 ~ 32 or 1 ~ 64.All
Loops
2Error in 1 Scan Loop NumberNo error in the value, PID operation can be omitted if the setting value (SV) is too small.All
Loops
3Error in Operation TypeA value is neither 0 or 1.Each
Loop
4Error in Sampling Interval (Ts)A value is out of the range, 1 ~ 6,000.Each
Loop
5Error in Proportional Gain (Kp)A value is out of the range, 1 ~ 10,000.Each
Loop
6Error in Integral Gain (Ki)A value is out of the range, 0 ~ 30,000.Each
Loop
7Error in Derivative Gain (Kd)A value is out of the rage, 0 ~ 30,000.Each
Loop
8Error in Filter Coefficient αA value is out of the range, 0 ~ 100.Each
Loop
9Error in Low Limit Manipulation Value (MVLL)A value is out of the range, 0 ~ 16,000.Each
Loop
10Error in High Limit Manipulation Value (MVHL)A value is out of the range, 0 ~ 16,000.Each
Loop
11Error in Variation Rate Limit of Manipulation Value (ΔMVL)A value is out of the range, 0 ~ 16,000.Each
Loop
12Error in Applying Manipulation ValueA value is neither 0 or 1.Each
Loop
13Error in Set Value Transition StepA value is out of the range, 0 ~ 1,000.Each
Loop

PIDINIT Operation Status

Bit NumberStatus
0PID-INIT OK
1PID CALC
2CALC DELAY
3ON/OFF STATUS
4WAIT LOOP INIT
5AUTO-TUNE INSTRUCTION
6AUTO-TUNING
7Reserved
8Reserved
9Reserved
10Reserved
11Reserved
12Reserved
13Reserved
14Reserved
15AUTO-TUNE ERROR