Configuration

Step 1: In the menu bar, left click Home and left click New Project.

PLC CPU Micro Analog Manual New Project

Optionally, in the menu bar left click File and left click New Project.

PLC CPU Micro Analog Manual Select CPU

Step 2: Left click PLC-FB and then left click next.

PLC CPU Micro Analog Manual Project Creation Details

Step 3: Left-click Series No. to change from PLC-FB0808 to PLC-FB1616.

Step 4: Left-click OK.

CPU Micro Analog Manual PLC Parameter in MapleLogic

Step 5: In the Project Window, expand Parameter and double left click PLC Parameter.

CPU Micro Analog Manual Analog IO Tab in MapleLogic

Step 6: In the PLC Parameter window, left click Analog I/O.

  • Channel 1 and channel 2 can be configured here.
  • The Device Setting option will be the starting data register type and number for all analog operations.

Device Setting

  • The device setting designated the starting data register address where the analog value is updated.
  • 20 WORDs are occupied from the starting data register address.
    • Each WORD can read or write data.
    • The remaining offsets not mentioned in the table below are not used.

Enable/Disable

  • To enable the channel for analog input/output, set the value to enabled.
  • To disable the channel for analog input/output, set the value to disabled.

Input

  • The input signal range sets the range for voltage or current input.
  • The ranges are as follows:
    • Voltage:
      • 0V ~ +5V
      • 0V ~ +10V
      • +1V ~ +5V
      • +1V ~ +10V
    • Current:
      • 0mA ~ 20mA
      • 4mA ~ 20mA

Average Count

  • If the analog input value can be filtered by the moving window filtering feature, it is possible to set the number of sampling data in the average count field
  • The number of samples can range from 1 ~ 255.
    • If the averaging count is set to 0, the moving window filtering feature is disabled.

AD Filter Coefficient (%)

  • This is used to set the AD filter coefficient percentage.

AD Max Digit

  • This is the maximum digital value for the analog input.

Stop Mode

  • If the value of the stop value mode is set to hold, the value will be retained when the PLC is switched to STOP mode.
  • If the value of the stop mode is set to clear, the value will NOT be retained when the PLC is switched to STOP mode.

Output

  • The output signal range sets the range for voltage or current output.
  • The ranges are as follows:
    • Voltage: 0V ~ +10V
    • Current: 4mA ~ 20mA

DA Max Digit

  • This is the maximum digital value from the output.

Analog Data Register Offset

  • After selecting the starting data register, the following offsets are used to read/write values:
OffsetDescriptionRangeReadWrite
0Channel 1 AD Input Value0 ~ 4,000 (16,000 SW)
1Channel 2 AD Input Value0 ~ 4,000 (16,000 SW)
2Channel 1 DA Output Value0 ~ 4,000 (16,000 SW)
3Channel 2 DA Output Value0 ~ 4,000 (16,000 SW)
4Error CodeRefer here
5Channel 1 AD Measured ValueDepends on configuration
6Channel 2 AD Measured ValueDepends on configuration
7Channel 1 AD Percentage Value0 ~ 1,000
(0% ~ 100%)
8Channel 2 AD Percentage Value0 ~ 1,000
(0% ~ 100%)
9Reserved
10Channel 1 DA Signal ValueDepends on configuration
11Channel 2 DA Signal ValueDepends on configuration
12Reserved
13Reserved
14Reserved
15Reserved
16Reserved
17Reserved
18Reserved
19Reserved

Error

Error CodeDescription
1Input Type Error
2Output Type Error
3AD Disconnection Error
+1V ~ +5V/+10V: Less than 0.2V
4mA ~ 20mA: Less than 0.8mA

AD Measured Value

  • This displays the measured analog value according to the range configuration.
Input RangeMinimum ValueMaximum Value
0V ~ +5V0500
0V ~ +10V01,000
+1V ~ +5V100500
+1V ~ +10V1001,000
0mA ~ 20mA02,000
4mA ~ 20mA4002,000

DA Signal Value

  • This displays the DA output value according to the range and the voltage/current configuration.
Output RangeMinimum ValueMaximum Value
0V ~ +10V01,000
4mA ~ 20mA4002,000

Switch Configuration

The PLC-FB1616 series has two sets of switches on either side of the serial communication port.

  • The switch on the right is the important switch.
    • To measure current for either channel 1 or 2, flip respective the switch up (I)
    • To measure voltage for either channel 1 or 2, flip respective the switch down (V).