Thermocouple (TC) Navigate to Online → Special Module Setup → TC Module or click on the TC module within the Card Properties. Applied Modules IO-SA0400T TC Module Step 1: Hold CTRL to configure all channels at once. Step 2: Click Setup to configure the TC type, digital value range, offset, digital filter constant, or average time. TC Type K J E T…
Thermocouple Module Features The IO-SA0400T is a thermocouple module that directly connects 8 thermocouples to a thermocouple input module. The module converts the temperature (°C or °F) by the first decimal digit and outputs a digital value between 0 ~ 16,000. The following are the thermocouples: K J E T B R S N The…
Consecutively Changing An analog value is a consecutively changing value, such as voltage, current, temperature, velocity, pressure, and flow rate. For example, a temperature value is consecutively changing with time.However, as the changing temperature value is directly input into the PLC, its equivalent analog amount of DC voltage (0V ~ +10V) or DC current (4mA ~ 20mA) is input into the PLC via…
Thermocouple Module General Specifications SpecificationDescriptionStandardsOperating Temperature-10°C ~ 65°C14°F ~ 149°F-Storage Temperature-25°C ~ 80°C-13°F ~ 176°F-Operating Humidity5% ~ 95% RH, Non-condensing-Storage Humidity5% ~ 95% RH, Non-condensing- Intermittent Vibration FrequencyAccelerationAmplitudeTimes5Hz ≤ f < 9Hz-3.5mm10 times in X, Y, and Z9Hz ≤ f ≤ 150Hz9.8m/s2 (1G)-10 times in X, Y, and Z Standard IEC 61131-2 Continuous Vibration FrequencyAccelerationAmplitudeTimes5Hz…
IO-SA0400T Functions Thermocouple Conversion Enable/Disable Thermocouple conversion can be enabled or disabled for each channel. For unused channels, users can make the conversion time short by setting them to disabled. Temperature Detection Value The temperature detection value saves a converted Celsius and Fahrenheit value into memory. This is down to the first decimal point ×…
IO-SA0400T Internal I/O Table InputName of SignalOutputName of SignalXn.0TC Module ReadyYn.0ReservedXn.1TC Conversion completion flagYn.1ReservedXn.2Set value saving completion flagYn.2Requesting to save set valueXn.3ReservedYn.3ReservedXn.4ReservedYn.4ReservedXn.5ReservedYn.5ReservedXn.6ReservedYn.6ReservedXn.7ReservedYn.7ReservedXn.8ReservedYn.8ReservedXn.9ReservedYn.9ReservedXn.AReservedYn.AReservedXn.BReservedYn.BReservedXn.CReservedYn.CReservedXn.DReservedYn.DReservedXn.EReservedYn.EReservedXn.FTC Module Error FlagYn.FRequesting to Clear Error Flag Input Signal Data RegisterSignal NameDescriptionXn.0TC Module ReadyThis signal is turned ON at the time TC conversion is completely ready (CPU power is ON).Xn.1TC Conversion Completion Flag-…
To write to buffer memory, use the TO instruction. To read from buffer memory, use the FROM instruction. Please refer to the table below for writing to and reading from buffer memory. Memory Address(Hexadecimal)Memory Address(Decimal)DetailsReadWrite00H0TC conversion Enable/Disable✓✓01H1Channel 1 Temperature detection value (°C)✓-02H2Channel 2 Temperature detection value (°C)✓-03H3Channel 3 Temperature detection value (°C)✓-04H4Channel 4 Temperature detection…
IO-SA0400T Troubleshooting RUN LED Light Blinking (0.2 seconds) If the RUN LED light is blinking every 0.2 seconds, check the error code in the module status window of MapleLogic. The error code is displayed as 0, 1, 2, 3, or 10. RUN LED Light Blinking (0.2 seconds) & Error Code 2 is Displayed The TC…
IO-SA0400T Wiring ChannelPositive (+) TerminalNegative (-) TerminalChannel 1Terminal 1Terminal 2Channel 2Terminal 3Terminal 4Channel 3Terminal 5Terminal 6Channel 4Terminal 7Terminal 8 ChannelTerminalAGNDTerminal 924V ExternalConnection on bottom of module