The leader in industrial automation and control solutions

HMC3-M0808Y0401T-V2

This module is an input/output module for ONLY the HMC2000 and HMC4000 Series models. It has eight bidirectional inputs, two pairs of which are high-speed inputs. It also has eight outputs, two sourcing (PNP) which can be configured for PWM operation and the other 6 are relay type.

This module also has 4 universal analog inputs (Voltage/Current/Thermocouple/RTD) as well as one analog output (Voltage/Current).

[Note: HMC3 I/O Module V2 Series are only compatible with HMC2000/ HMC4000 Series Base Model]

8 Digital Inputs (2 high-speed pairs up to 200kHz)

8 Digital Outputs (6 Relay, 2 PNP w/ 2 PWM up to 200kHz)

4 Universal Analog Inputs

  • Voltage: 0-5V, 0-10V
  • Current: 0-20mA, 4-20mA
  • Thermocouple
  • RTD

1 Analog Output

  • Voltage: 0-5V, 0-10V
  • Current: 0-20mA, 4-20mA
HMC3-M0808Y0401T-V2 Module
Specifications
               Power12V and 3.3VDC from base
               CertificationsCE, UL
Digital Inputs8 bidirectional inputs (2 high-speed pairs)
               Rated Input Voltage24 VDC +/- 15%
               Rated input currentUp to 5mA (per contact)
               Input impedance4.9K ohms
               Minimum ON voltage15 VDC
               Maximum OFF voltage5 VDC
               Turn ON Time10 mSec
               Turn OFF Time10 mSec
               IsolationOptically isolated from internal circuit
Analog Inputs4 Inputs, each configurable as:
0 to 50mV, 0 to 100 mV; 0 to 10V, 0 to 5V;
0 to 20mA, 4-20mA;
PT100 RTD, alpha1 [0.00385 Ω/Ω°C] (-200 to 850 C);
PT100 RTD, alpha2 [0.003926 Ω/Ω°C] (-100 to 457 C);
PT1000 RTD (-200 to 850 C);
Type J Thermocouple (-210 to 1200 C);
Type K Thermocouple (-200 to 1373 C)
               Input Resolution16 bit
               Input Impedance3 KΩ
               Input AccuracyOverall Accuracy 0.2% of full scale@25°C (max)
Digital Outputs8 outputs: 6 Relay, 2 Sourcing (PNP-type) / 2 PWM
               Maximum PWM Output Frequency200KHz
               Minimum ON Output Voltage22 VDC
               Maximum ON Output Voltage30 VDC
               Minimum OFF Output Voltage0.2 VDC
               Maximum OFF Output Voltage1 VDC
               Rated Load250mA @ 24VDC
2A @230VAC
               Nominal load96W 6W (resistive) @ 24VDC 6VA (inductive, UPF)
Analog Outputs1, configurable as:
0 to 5V, 0 to 10V;
0 to 20mA, 4-20mA
               AccuracyOverall Accuracy 0.2% of full scale@25°C (max)
               Load1 KΩ (Min) for V;
500Ω (Max) for mA
               Output Resolution12 bit
High-speed Channels 
               No. of inputs2 channel pairs (X0/X1 and X2/X3)
               Maximum Input Frequency200 KHz
               Maximum Input Count4,294,967,295 (32-bit)
General 
               Connection methodRemovable terminals (3.81 mm pitch)
               Operating Temperature0 to 55°C
               Operating Humidity10% to 90% (non-condensing)
               Mechanical Dimension (W x H x D)1.88 x 4.25 x 1.61 inches [48x108x41mm]

Configuration

Use MAPware-7000 to assign input (X and XW), output (Y and YW) and configuration (M and MW) memory addresses to the module. These addresses are created according to the slot location of the module, where nn refers to the slot number (ex. 01…05):

FunctionRegisterAccess
X0-X7 Digital InputsXnn000-007 (XWnn00)Read Only
Y0-Y7 Digital OutputsYnn000-007 (YWnn00)Read/Write
High-speed Counter OptionHSC Channel 1HSC Channel 2 
HSC Input PinX0X2Read Only
Quadrature InputsPair 1Pair 2 
Counter InputsX0, X1X2, X3Read Only
HSC Configuration RegisterMWnn00MWnn06Read/Write
HSC Counter Register (Current Value)MWnn01MWnn07Read/Write
HSC Preset RegisterMWnn03MWnn09Read/Write
HSC Enable BitMnn080Mnn176Read/Write
HSC Reset BitMnn081Mnn177Read/Write
Output FlagY2Y3 
PWM OutputsChannel 1Channel 2 
OutputY0Y1Read Only
PWM Configuration RegisterMWnn24MWnn30Read/Write
Frequency Setting RegisterMWnn25MWnn31Read/Write
ON Duty Setting Register (Duty Cycle)MWnn27MWnn33Read/Write
Pulse Enable FlagMnn576Mnn577Read/Write
ON Duty Setting Error FlagMnn466Mnn471Read Only
Frequency Setting Error FlagMnn467Mnn472Read Only
Analog InputsRegister 
Input Channel 0 DataXWnn11Read Only
Input Channel 1 DataXWnn13Read Only
Input Channel 2 DataXWnn15Read Only
Input Channel 3 DataXWnn17Read Only
Input Channel 0 Config RegisterMWnn60Read/Write
Input Channel 1 Config RegisterMWnn61Read/Write
Input Channel 2 Config RegisterMWnn62Read/Write
Input Channel 3 Config RegisterMWnn63Read/Write
Analog OutputsRegister 
Output Channel 0 Data (Voltage)YWnn01Read/Write
Output Channel 0 Data (Current)YWnn02Read/Write
Output Channel 0 Config RegisterMWnn68Read/Write

Reference the table below when configuring each HSC Configuration Register:

Input ModeOutput ModeRegister Value
Normal InputN/A0
High Speed, Single Phase, Up/Down CounterOutput ON when preset is reached2
Output ON when counter is enabled,
OFF when preset is reached
258
Quadrature 4XOutput ON when preset is reached131
Output ON when counter is enabled,
OFF when preset is reached
387

Reference the table below when configuring the PWM Configuration Registers:

Output ModeRegister Value
Normal PWM (fixed frequency)1
Normal PWM (variable frequency)2
CW/CCW (fixed frequency)3
CW/CCW (variable frequency)4
Pulse/Direction (fixed frequency)7
Pulse/Direction (variable frequency)8
Trapezoidal (Fixed Pulse Mode)9

Reference the table below when configuring each Analog Input Configuration Register (MWnn60-MWnn63):

Input Signal Type Register Value
Voltage, 0 to 10V 1
Voltage, 0 to 5V 6
Voltage, 0 to 50mV 5
Voltage, 0 to 100mV 4
Current, 4 to 20mA 2
Current, 0 to 20mA 3
RTC and ThermocoupleFor °C
RTD, PT100, alpha1 17
RTD, PT100, alpha2 18
RTD, PT10009
Thermocouple, Type J 214
Thermocouple, Type K 215

Notes:

  1. alpha1= 0.00385 Ω/Ω°C, alpha2=0.003926 Ω/Ω°C
  2. 15-minute module warm-up time recommended

The values in the appropriate analog input register range from 0-65535.

Expansion Module Register ValueInput Values
0 to 20mA4 to 20mA0 to 10V0 to 5V0 to 100mV0 to 50mV
00mA4mA0V0V0mV0mV
163845mA8mA2.5V1.25V25mV12.5mV
3276810mA12mA5V2.5V50mV25mV
4915215mA16mA7.5V3.75V75mV37.5mV
6553520mA20mA10V5V100mV50mV

Reference the table below when configuring the Analog Output Configuration Register (MWnn68):

Output Signal TypeRegister Value
Voltage, 0 to 10V2
Voltage, 0 to 5V1
Current, 4 to 20mA5
Current, 0 to 20mA6

Analog expansion modules have an analog output resolution of 12 bits with values ranging from 0-4095.

Expansion Module Reg ValueOutput Values
0 to 10V4 to 20mA
004mA
10242.5V8mA
20485V12mA
30727.5V16mA
409510V20mA

Wiring Diagrams

Digital Inputs

HMC3-M0808Y0401T-V2 Module Digital Input Wiring Diagram

Digital Outputs

HMC3-M0808Y0401T-V2 Module Digital Output Wiring Diagram

Analog Input: Voltage

HMC3-M0808Y0401T-V2 Module Voltage Input Wiring Diagram

Analog Input: Current

HMC3-M0808Y0401T-V2 Module Current Input Wiring Diagram

Analog Input: mV / Thermocouple

HMC3-M0808Y0401T-V2 Module mV/Thermocouple Input Wiring Diagram

Analog Input: RTD

HMC3-M0808Y0401T-V2 Module RTD Input Wiring Diagram

Analog Output: Voltage

HMC3-M0808Y0401T-V2 Module Analog Voltage Output Wiring Diagram

Analog Output: Current

HMC3-M0808Y0401T-V2 Module Analog Current Output Wiring Diagram

HSC Single Phase Up Counter

HSC Single Phase Up Counter Wiring Diagram

HSC Single Phase Down Counter

HSC Single Phase Down Counter Wiring Diagram

HSC Quadrature

HSC Quadrature Counter

HMC3-M1212P0200 V2

This module is an input/output module for the HMC2000 and HMC4000 Series models. It has twelve digital inputs, two of which are high-speed pairs and 12 sourcing digital outputs. One of those digital outputs are configurable as PWM.

This module also has two analog inputs, each measuring Voltage or Current.

[Note: HMC3 I/O Module V2 Series are only compatible with HMC2000/ HMC4000 Series Base Model]

12 Digital Inputs (2 high-speed pairs up to 200kHz)

12 Digital Outputs (1 PWM up to 1kHz)

2 Analog Inputs

  • Voltage: 0-5V, 0-10V
  • Current: 0-20mA, 4-20mA
HMC3-M1212P0200-V2 Module
Specifications
               Power12 VDC from base
               CertificationsCE, UL
Digital Inputs12 bidirectional inputs (2 high-speed pairs)
               Rated Input Voltage24 VDC +/- 15%
               Rated input currentUp to 5mA (per contact)
               Input impedance4.9K ohms
               Minimum ON voltage15 VDC
               Maximum OFF voltage5 VDC
               Turn ON Time10 mSec
               Turn OFF Time10 mSec
               IsolationOptically isolated from internal circuit
Analog Inputs2 Inputs, each configurable as:
0 to 10V, 0 to 5V;
0 to 20mA, 4-20mA
               Input Resolution16 bit
               Input Impedance3 KΩ
               Input AccuracyOverall Accuracy 0.2% of full scale@25°C (max)
Digital Outputs12 sourcing outputs (PNP-type), 1 PWM
               Maximum PWM Output Frequency1KHz
               Minimum ON Output Voltage22 VDC
               Maximum ON Output Voltage30 VDC
               Minimum OFF Output Voltage0.2 VDC
               Maximum OFF Output Voltage1 VDC
               Rated Load250mA @ 24VDC
               Nominal load96W 6W (resistive) @ 24VDC
6VA (inductive, UPF)

High-speed Channels
 
               No. of inputs2 channel pairs (X0/X1 and X2/X3)
               Maximum Input Frequency200 KHz
               Maximum Input Count4,294,967,295 (32-bit)
General 
               Connection methodRemovable terminals (3.81 mm pitch)
               Operating Temperature0 to 55°C
               Operating Humidity10% to 90% (non-condensing)
               Mechanical Dimension (W x H x D)1.88 x 4.25 x 1.61 inches [48x108x41mm]

Configuration

Use MAPware-7000 to assign input (X and XW), output (Y and YW) and configuration (M and MW) memory addresses to the module. These addresses are created according to the slot location of the module, where nn refers to the slot number (ex. 01…05):

FunctionRegisterAccess
X0-X11 Digital InputsXnn000-011 (XWnn00)Read Only
Y0-Y11 Digital OutputsYnn000-011 (YWnn00)Read/Write
High-speed Counter OptionHSC Channel 1HSC Channel 2 
HSC Input PinX0X2Read Only
Quadrature InputsPair 1Pair 2 
Counter InputsX0, X1X2, X3Read Only
HSC Configuration RegisterMWnn00MWnn06Read/Write
HSC Counter Register (Current Value)MWnn01MWnn07Read/Write
HSC Preset RegisterMWnn03MWnn09Read/Write
HSC Enable BitMnn080Mnn176Read/Write
HSC Reset BitMnn081Mnn177Read/Write
Output FlagY2Y3 
PWM OutputsChannel 1 
OutputY0 Read Only
PWM Configuration RegisterMWnn24 Read/Write
Frequency Setting RegisterMWnn25 Read/Write
ON Duty Setting Register (Duty Cycle)MWnn27 Read/Write
Pulse Enable FlagMnn576 Read/Write
ON Duty Setting Error FlagMnn466 Read Only
Frequency Setting Error FlagMnn467 Read Only
Analog InputsRegister 
Input Channel 0 DataXWnn11Read Only
Input Channel 1 DataXWnn13Read Only
Input Channel 0 Config RegisterMWnn60Read/Write
Input Channel 1 Config RegisterMWnn61Read/Write

Reference the table below when configuring each HSC Configuration Register:

Input ModeOutput ModeRegister Value
Normal InputN/A0
High Speed, Single Phase, Up/Down CounterOutput ON when preset is reached2
Output ON when counter is enabled,
OFF when preset is reached
258
Quadrature 4XOutput ON when preset is reached131
Output ON when counter is enabled,
OFF when preset is reached
387

Reference the table below when configuring the PWM Configuration Registers:

Output ModeRegister Value
Normal PWM (fixed frequency)1
Normal PWM (variable frequency)2
CW/CCW (fixed frequency)3
CW/CCW (variable frequency)4
Pulse/Direction (fixed frequency)7
Pulse/Direction (variable frequency)8
Trapezoidal (Fixed Pulse Mode)9

Reference the table below when configuring each Analog Input Configuration Register (MWnn60-MWnn61):

Input Signal TypeRegister Value
Voltage, 0 to 10V1
Voltage, 0 to 5V6
Current, 4 to 20mA2
Current, 0 to 20mA3

The values in the appropriate analog input register range from 0-65535.

Expansion Module Register ValueInput Values
0 to 20mA4 to 20mA0 to 10V0 to 5V
00mA4mA0V0V
163845mA8mA2.5V1.25V
3276810mA12mA5V2.5V
4915215mA16mA7.5V3.75V
6553520mA 20mA 10V 5V

Wiring

Digital Inputs

HMC3-M1212P0200-V2 Digital Input Wiring Diagram

Digital Outputs

HMC3-M1212P0200-V2 Digital Output Wiring Diagram

Analog Input (Voltage)

HMC3-M1212P0200-V2 Analog Voltage Input Wiring Diagram

Analog Input (Current)

HMC3-M1212P0200-V2 Analog Current Input Wiring Diagram

HSC Single Phase Up Counter

HSC Single Phase Up Counter Wiring Diagram

HSC Single Phase Down Counter

HSC Single Phase Down Counter Wiring Diagram

HSC Quadrature

HSC Quadrature Counter

HMC3-M1212Y0200 V2

This module is an input/output module for the HMC2000 and HMC4000 Series models.  It has eight digital inputs, two of which are high speed pairs and 12 digital outputs.  Two of those digital outputs are sourcing (PNP), and 1 can be configured for PWM, and the other 10 outputs are relay type.

This module also has two analog inputs, each measuring Voltage or Current.

[Note: HMC3 I/O Module V2 Series are only compatible with HMC2000/ HMC4000 Series Base Model]

12 Digital Inputs (2 high-speed pairs up to 200kHz)

12 Digital Outputs (1 PWM up to 1kHz)

2 Analog Inputs

  • Voltage: 0-5V, 0-10V
  • Current: 0-20mA, 4-20mA
HMC3-M1212P0200-V2 Module

Specifications
               Power12 VDC from base
               CertificationsCE, UL
Digital Inputs12 bidirectional inputs (2 high-speed pairs)
               Rated Input Voltage24 VDC +/- 15%
               Rated input currentUp to 5mA (per contact)
               Input impedance4.9K ohms
               Minimum ON voltage15 VDC
               Maximum OFF voltage5 VDC
               Turn ON Time10 mSec
               Turn OFF Time10 mSec
               IsolationOptically isolated from internal circuit
Analog Inputs2 Inputs, each configurable as:
0 to 10V, 0 to 5V;
0 to 20mA, 4-20mA
               Input Resolution16 bit
               Input Impedance3 KΩ
               Input AccuracyOverall Accuracy 0.2% of full scale@25°C (max)
Digital Outputs12 outputs: 10 Relay, 2 Sourcing (PNP-type), 1 PWM
               Maximum Output Frequency1KHz
               Minimum ON Output Voltage22 VDC
               Maximum ON Output Voltage30 VDC
               Minimum OFF Output Voltage0.2 VDC
               Maximum OFF Output Voltage1 VDC
               Rated Load250mA @ 24VDC
2A @230VAC
               Nominal load96W 6W (resistive) @ 24VDC 6VA (inductive, UPF)

High-speed Channels
 
               No. of inputs2 channel pairs (X0/X1 and X2/X3)
               Maximum Input Frequency200 KHz
               Maximum Input Count4,294,967,295 (32-bit)
General 
               Connection methodRemovable terminals (3.81 mm pitch)
               Operating Temperature0 to 55°C
               Operating Humidity10% to 90% (non-condensing)
               Mechanical Dimension (W x H x D)1.88 x 4.25 x 1.61 inches [48x108x41mm]

Configuration

Use MAPware-7000 to assign input (X and XW), output (Y and YW) and configuration (M and MW) memory addresses to the module. These addresses are created according to the slot location of the module, where nn refers to the slot number (ex. 01…05):

FunctionRegisterAccess
X0-X11 Digital InputsXnn000-011 (XWnn00)Read Only
Y0-Y11 Digital OutputsYnn000-011 (YWnn00)Read/Write
High-speed Counter OptionHSC Channel 1HSC Channel 2 
HSC Input PinX0X2Read Only
Quadrature InputsPair 1Pair 2 
Counter InputsX0, X1X2, X3Read Only
HSC Configuration RegisterMWnn00MWnn06Read/Write
HSC Counter Register (Current Value)MWnn01MWnn07Read/Write
HSC Preset RegisterMWnn03MWnn09Read/Write
HSC Enable BitMnn080Mnn176Read/Write
HSC Reset BitMnn081Mnn177Read/Write
Output FlagY2Y3 
PWM OutputsChannel 1 
OutputY0 Read Only
PWM Configuration RegisterMWnn24 Read/Write
Frequency Setting RegisterMWnn25 Read/Write
ON Duty Setting Register (Duty Cycle)MWnn27 Read/Write
Pulse Enable FlagMnn576 Read/Write
ON Duty Setting Error FlagMnn466 Read Only
Frequency Setting Error FlagMnn467 Read Only
Analog InputsRegister 
Input Channel 0 DataXWnn11Read Only
Input Channel 1 DataXWnn13Read Only
Input Channel 0 Config RegisterMWnn60Read/Write
Input Channel 1 Config RegisterMWnn61Read/Write

Reference the table below when configuring each HSC Configuration Register:

Input ModeOutput ModeRegister Value
Normal InputN/A0
High Speed, Single Phase, Up/Down CounterOutput ON when preset is reached2
Output ON when counter is enabled,
OFF when preset is reached
258
Quadrature 4XOutput ON when preset is reached131
Output ON when counter is enabled,
OFF when preset is reached
387

Reference the table below when configuring the PWM Configuration Registers:

Output ModeRegister Value
Normal PWM (fixed frequency)1
Normal PWM (variable frequency)2
CW/CCW (fixed frequency)3
CW/CCW (variable frequency)4
Pulse/Direction (fixed frequency)7
Pulse/Direction (variable frequency)8
Trapezoidal (Fixed Pulse Mode)9

Reference the table below when configuring each Analog Input Configuration Register (MWnn60-MWnn61):

Input Signal TypeRegister Value
Voltage, 0 to 10V1
Voltage, 0 to 5V6
Current, 4 to 20mA2
Current, 0 to 20mA3

The values in the appropriate analog input register range from 0-65535.

Expansion Module Register ValueInput Values
0 to 20mA4 to 20mA0 to 10V0 to 5V
00mA4mA0V0V
163845mA8mA2.5V1.25V
3276810mA12mA5V2.5V
4915215mA16mA7.5V3.75V
6553520mA 20mA 10V 5V

Wiring

Digital Input

HMC3-M1212Y0200-V2 Digital Input Wiring Diagram

Digital Output

HMC3-M1212Y0200-V2 Digital Output Wiring Diagram

Analog Input (Voltage)

HMC3-M1212Y0200-V2 Analog Voltage Input Wiring Diagram

Analog Input (Current)

HMC3-M1212Y0200-V2 Analog Current Input Wiring Diagram

HSC Single Phase Up Counter

HSC Single Phase Up Counter Wiring Diagram

HSC Single Phase Down Counter

HSC Single Phase Down Counter Wiring Diagram

HSC Quadrature

HSC Quadrature Counter

HMC3-M1210P0201 V2

This module is an input/output module for the HMC2000 and HMC4000 Series models. It has twelve digital inputs, two of which are high-speed pairs and 10 sourcing (PNP) digital outputs. One of those digital outputs are PWM.

This module also has two analog inputs (Voltage/Current) and one analog output (Voltage/Current).

[Note: HMC3 I/O Module V2 Series are only compatible with HMC2000/ HMC4000 Series Base Model]

12 Digital Inputs (2 high-speed pairs up to 200kHz)

10 Digital Outputs (1 PWM up to 1kHz)

2 Analog Inputs

  • Voltage: 0-5V, 0-10V
  • Current: 0-20mA, 4-20mA

1 Analog Output

  • Voltage: 0-5V, 0-10V
  • Current: 0-20mA, 4-20mA
HMC3-M1210P0201-V2 Module
Specifications
               Power12 VDC from base
               CertificationsCE, UL
Digital Inputs12 bidirectional inputs (2 high-speed pairs)
               Rated Input Voltage24 VDC +/- 15%
               Rated input currentUp to 5mA (per contact)
               Input impedance4.9K ohms
               Minimum ON voltage15 VDC
               Maximum OFF voltage5 VDC
               Turn ON Time10 msec
               Turn OFF Time10 msec
               IsolationOptically isolated from internal circuit
Analog Inputs2 Inputs, each configurable as:
0 to 10V, 0 to 5V;
0 to 20mA, 4-20mA
               Input Resolution16 bit
               Input Impedance3 KΩ
               Input AccuracyOverall Accuracy 0.2% of full scale@25°C (max)
Digital Outputs10 sourcing outputs (PNP-type), 2 PWM
               Maximum PWM Output Frequency1KHz
               Minimum ON Output Voltage22 VDC
               Maximum ON Output Voltage30 VDC
               Minimum OFF Output Voltage0.2 VDC
               Maximum OFF Output Voltage1 VDC
               Rated Load250mA @ 24VDC
               Nominal load96W 6W (resistive) @ 24VDC
6VA (inductive, UPF)
Analog Outputs1, configurable as:
0 to 5V, 0 to 10V;
0 to 20mA, 4-20mA
               AccuracyOverall Accuracy 0.2% of full scale@25°C (max)
               Load1 KΩ (Min) for V;
500Ω (Max) for mA
               Output Resolution12 bit
High-speed Channels 
               No. of inputs2 channel pairs (X0/X1 and X2/X3)
               Maximum Input Frequency200 KHz
               Maximum Input Count4,294,967,295 (32-bit)
General 
               Connection methodRemovable terminals (3.81 mm pitch)
               Operating Temperature0 to 55°C
               Operating Humidity10% to 90% (non-condensing)
               Mechanical Dimension (W x H x D)1.88 x 4.25 x 1.61 inches [48x108x41mm]

Configuration

Use MAPware-7000 to assign input (X and XW), output (Y and YW) and configuration (M and MW) memory addresses to the module. These addresses are created according to the slot location of the module, where nn refers to the slot number (ex. 01…05):

The values in the appropriate analog input register range from 0-65535, while analog output register values range from 0-4095.

FunctionRegisterAccess
X0-X11 Digital InputsXnn000-011 (XWnn00)Read Only
Y0-Y9 Digital OutputsYnn000-009 (YWnn00)Read/Write
High-speed Counter OptionHSC Channel 1HSC Channel 2 
HSC Input PinX0X2Read Only
Quadrature InputsPair 1Pair 2 
Counter InputsX0, X1X2, X3Read Only
HSC Configuration RegisterMWnn00MWnn06Read/Write
HSC Counter Register (Current Value)MWnn01MWnn07Read/Write
HSC Preset RegisterMWnn03MWnn09Read/Write
HSC Enable BitMnn080Mnn176Read/Write
HSC Reset BitMnn081Mnn177Read/Write
Output FlagY2Y3 
PWM OutputsChannel 1Channel 2 
OutputY0Y1Read Only
PWM Configuration RegisterMWnn24MWnn30Read/Write
Frequency Setting RegisterMWnn25MWnn31Read/Write
ON Duty Setting Register (Duty Cycle)MWnn27MWnn33Read/Write
Pulse Enable FlagMnn576Mnn577Read/Write
ON Duty Setting Error FlagMnn466Mnn471Read Only
Frequency Setting Error FlagMnn467Mnn472Read Only
Analog InputsRegister 
Input Channel 0 DataXWnn11Read Only
Input Channel 1 DataXWnn13Read Only
Input Channel 0 Config RegisterMWnn60Read/Write
Input Channel 1 Config RegisterMWnn61Read/Write
Analog OutputsRegister 
Output Channel 0 Data (Voltage)YWnn01Read/Write
Output Channel 0 Data (Current)YWnn02Read/Write
Output Channel 0 Config RegisterMWnn68Read/Write

Reference the table below when configuring each HSC Configuration Register:

Input ModeOutput ModeRegister Value
Normal InputN/A0
High Speed, Single Phase, Up/Down CounterOutput ON when preset is reached2
Output ON when counter is enabled,
OFF when preset is reached
258
Quadrature 4XOutput ON when preset is reached131
Output ON when counter is enabled,
OFF when preset is reached
387

Reference the table below when configuring the PWM Configuration Registers:

Output ModeRegister Value
Normal PWM (fixed frequency)1
Normal PWM (variable frequency)2
CW/CCW (fixed frequency)3
CW/CCW (variable frequency)4
Pulse/Direction (fixed frequency)7
Pulse/Direction (variable frequency)8
Trapezoidal (Fixed Pulse Mode)9

Reference the tables below when configuring each Analog Input and Output Configuration Register:

Input Signal TypeRegister Value
Voltage, 0 to 10V1
Voltage, 0 to 5V6
Current, 4 to 20mA2
Current, 0 to 20mA3
Output Signal TypeRegister Value
Voltage, 0 to 10V2
Voltage, 0 to 5V1
Current, 4 to 20mA5
Current, 0 to 20mA6
Expansion Module Register ValueInput Values
0 to 20mA4 to 20mA0 to 10V0 to 5V
00mA4mA0V0V
163845mA8mA2.5V1.25V
3276810mA12mA5V2.5V
4915215mA16mA7.5V3.75V
6553520mA20mA10V5V
Expansion Module Register ValueOutput Values
0 to 10V4 to 20mA
004mA
10242.5V8mA
20485V12mA
30727.5V16mA
409510V20mA

Wiring

Digital Inputs

HMC3-M1210P0201-V2 Module Digital Input Wiring Diagram

Digital Outputs

HMC3-M1210P0201-V2 Digital Output Wiring Diagram

Analog Input (Voltage)

HMC3-M1210P0201-V2 Module Analog Voltage Input Wiring Diagram

Analog Input (Current)

HMC3-M1210P0201-V2 Module Analog Current Input Wiring Diagram

Analog Output (Voltage)

HMC3-M1210P0201-V2 Module Analog Voltage Output Wiring Diagram

Analog Output (Current)

HMC3-M1210P0201-V2 Module Analog Current Output Wiring Diagram

HSC Single Phase Up Counter

HSC Single Phase Up Counter Wiring Diagram

HSC Single Phase Down Counter

HSC Single Phase Down Counter Wiring Diagram

HSC Quadrature

HSC Quadrature Counter

HMC3-M1210Y0201 V2

This module is an input/output module for the HMC2000 and HMC4000 Series models. It has twelve digital inputs, two of which are high-speed pairs and 10 sourcing (PNP) digital outputs. One of those digital outputs are PWM.

This module also has two analog inputs (Voltage/Current) and one analog output (Voltage/Current).

[Note: HMC3 I/O Module V2 Series are only compatible with HMC2000/ HMC4000 Series Base Model]

12 Digital Inputs (2 high-speed pairs up to 200kHz)

10 Digital Outputs (8 Relay, 2 PNP w/ 1 PWM up to 1kHz)

2 Analog Inputs

  • Voltage: 0-5V, 0-10V
  • Current: 0-20mA, 4-20mA

1 Analog Output

  • Voltage: 0-5V, 0-10V
  • Current: 0-20mA, 4-20mA
HMC3-M1210Y0201-V2 Module
Specifications
               Power12 VDC from base
               CertificationsCE, UL
Digital Inputs12 bidirectional inputs (2 high-speed pairs)
               Rated Input Voltage24 VDC +/- 15%
               Rated input currentUp to 5mA (per contact)
               Input impedance4.9K ohms
               Minimum ON voltage15 VDC
               Maximum OFF voltage5 VDC
               Turn ON Time10 msec
               Turn OFF Time10 msec
               IsolationOptically isolated from internal circuit
Analog Inputs2 Inputs, each configurable as:
0 to 10V, 0 to 5V;
0 to 20mA, 4-20mA
               Input Resolution16 bit
               Input Impedance3 KΩ
               Input AccuracyOverall Accuracy 0.2% of full scale@25°C (max)
Digital Outputs10 outputs: 8 Relay, 2 Sourcing (PNP-type)
               Maximum PWM Output Frequency1KHz
               Minimum ON Output Voltage22 VDC
               Maximum ON Output Voltage30 VDC
               Minimum OFF Output Voltage0.2 VDC
               Maximum OFF Output Voltage1 VDC
               Rated Load250mA @ 24VDC
2A @230VAC
               Nominal load96 Ohms 6W (resistive) @ 24VDC
6VA (inductive, UPF)
Analog Outputs1, configurable as:
0 to 5V, 0 to 10V;
0 to 20mA, 4-20mA
               AccuracyOverall Accuracy 0.2% of full scale@25°C (max)
               Load1 KΩ (Min) for V;
500Ω (Max) for mA
               Output Resolution12 bit
High-speed Channels 
               No. of inputs2 channel pairs (X0/X1 and X2/X3)
               Maximum Input Frequency200 KHz
               Maximum Input Count4,294,967,295 (32-bit)
General 
               Connection methodRemovable terminals (3.81 mm pitch)
               Operating Temperature0 to 55°C
               Operating Humidity10% to 90% (non-condensing)
               Mechanical Dimension (W x H x D)1.88 x 4.25 x 1.61 inches [48x108x41mm]

Configuration

Use MAPware-7000 to assign input (X and XW), output (Y and YW) and configuration (M and MW) memory addresses to the module. These addresses are created according to the slot location of the module, where nn refers to the slot number (ex. 01…05):

FunctionRegisterAccess
X0-X11 Digital InputsXnn000-011 (XWnn00)Read Only
Y0-Y9 Digital OutputsYnn000-009 (YWnn00)Read/Write
High-speed Counter OptionHSC Channel 1HSC Channel 2 
HSC Input PinX0X2Read Only
Quadrature InputsPair 1Pair 2 
Counter InputsX0, X1X2, X3Read Only
HSC Configuration RegisterMWnn00MWnn06Read/Write
HSC Counter Register (Current Value)MWnn01MWnn07Read/Write
HSC Preset RegisterMWnn03MWnn09Read/Write
HSC Enable BitMnn080Mnn176Read/Write
HSC Reset BitMnn081Mnn177Read/Write
Output FlagY2Y3 
PWM OutputsChannel 1Channel 2 
OutputY0Read Only
PWM Configuration RegisterMWnn24Read/Write
Frequency Setting RegisterMWnn25Read/Write
ON Duty Setting Register (Duty Cycle)MWnn27Read/Write
Pulse Enable FlagMnn576Read/Write
ON Duty Setting Error FlagMnn466Read Only
Frequency Setting Error FlagMnn467Read Only
Analog InputsRegister 
Input Channel 0 DataXWnn11Read Only
Input Channel 1 DataXWnn13Read Only
Input Channel 0 Config RegisterMWnn60Read/Write
Input Channel 1 Config RegisterMWnn61Read/Write
Analog OutputsRegister 
Output Channel 0 Data (Voltage)YWnn01Read/Write
Output Channel 0 Data (Current)YWnn02Read/Write
Output Channel 0 Config RegisterMWnn68Read/Write

Reference the table below when configuring each HSC Configuration Register:

Input ModeOutput ModeRegister Value
Normal InputN/A0
High Speed, Single Phase, Up/Down CounterOutput ON when preset is reached2
Output ON when counter is enabled,
OFF when preset is reached
258
Quadrature 4XOutput ON when preset is reached131
Output ON when counter is enabled,
OFF when preset is reached
387

Reference the table below when configuring the PWM Configuration Registers:

Output ModeRegister Value
Normal PWM (fixed frequency)1
Normal PWM (variable frequency)2
CW/CCW (fixed frequency)3
CW/CCW (variable frequency)4
Pulse/Direction (fixed frequency)7
Pulse/Direction (variable frequency)8
Trapezoidal (Fixed Pulse Mode)9

Reference the tables below when configuring each Analog Input and Output Configuration Register:

Input Signal TypeRegister Value
Voltage, 0 to 10V1
Voltage, 0 to 5V6
Current, 4 to 20mA2
Current, 0 to 20mA3
Output Signal TypeRegister Value
Voltage, 0 to 10V2
Voltage, 0 to 5V1
Current, 4 to 20mA5
Current, 0 to 20mA6

The values in the appropriate analog input register range from 0-65535, while analog output register values range from 0-4095.

Expansion Module Register ValueInput Values
0 to 20mA4 to 20mA0 to 10V0 to 5V
00mA4mA0V0V
163845mA8mA2.5V1.25V
3276810mA12mA5V2.5V
4915215mA16mA7.5V3.75V
6553520mA20mA10V5V
Expansion Module Register ValueOutput Values
0 to 10V4 to 20mA
004mA
10242.5V8mA
20485V12mA
30727.5V16mA
409510V20mA

Wiring

Digital Inputs

HMC3-M1210Y0201-V2 Module Digital Input Wiring Diagram

Digital Outputs

HMC3-M1210Y0201-V2 Digital Output Wiring Diagram

Analog Input (Voltage)

HMC3-M1210Y0201-V2 Module Analog Voltage Input Wiring Diagram

Analog Input (Current)

HMC3-M1210Y0201-V2 Module Analog Current Input Wiring Diagram

Analog Output (Voltage)

HMC3-M1210Y0201-V2 Module Analog Voltage Output Wiring Diagram

Analog Output (Current)

HMC3-M1210P0201-V2 Module Analog Current Output Wiring Diagram

HSC Single Phase Up Counter

HSC Single Phase Up Counter Wiring Diagram

HSC Single Phase Down Counter

HSC Single Phase Down Counter Wiring Diagram

HSC Quadrature

HSC Quadrature Counter

HMC3-M1614Y V2

This module is a digital input/output module for the HMC2000 and HMC4000 Series models.

It has 16 digital inputs. The module also features 14 digital outputs, 2 sourcing (PNP) outputs with 1 capable of PWM operation and 12 relay type outputs.

[Note: HMC3 I/O Module V2 Series are only compatible with HMC2000/ HMC4000 Series Base Model]

16 Digital Inputs (2 high-speed pairs up to 200kHz)

14 Digital Outputs (12 Relay, 2 PNP w/ 1 PWM up to 1kHz)

HMC3-M1614Y-V2 I/O Module
Specifications
               Power3.3 VDC from HMC3000 base
               CertificationsCE, UL
Digital Inputs16 bidirectional inputs (2 high-speed pairs)
               Rated Input Voltage24 VDC +/- 15%
               Rated input currentUp to 5mA (per contact)
               Input impedance4.9K ohms
               Minimum ON voltage15 VDC
               Maximum OFF voltage5 VDC
               Turn ON Time10 mSec
               Turn OFF Time10 mSec
               IsolationOptically isolated from internal circuit
Digital Outputs14 outputs: 12 Relay, 2 Sourcing (PNP-type) / 1 PWM
               Maximum PWM Output Frequency1KHz
               Minimum ON Output Voltage22 VDC
               Maximum ON Output Voltage30 VDC
               Minimum OFF Output Voltage0.2 VDC
               Maximum OFF Output Voltage1 VDC
               Rated Load250mA @ 24VDC
2A @230VAC
               Nominal load96W 6W (resistive) @ 24VDC 6VA (inductive, UPF)
High-speed Channels 
               No. of inputs2 channel pairs (X0/X1 and X2/X3)
               Maximum Input Frequency200 KHz
               Maximum Input Count4,294,967,295 (32-bit)
General 
               Connection methodRemovable terminals (3.81 mm pitch)
               Operating Temperature0 to 55°C
               Operating Humidity10% to 90% (non-condensing)
               Mechanical Dimension (W x H x D)1.88 x 4.25 x 1.61 inches [48x108x41mm]
FunctionRegisterAccess
X0-X15 Digital InputsXnn000-015 (XWnn00)Read Only
Y0-Y13 Digital OutputsYnn000-013 (YWnn00)Read/Write

Configuration

Use MAPware-7000 to assign input (X and XW), output (Y and YW) and configuration (M and MW) memory addresses to the module. These addresses are created according to the slot location of the module, where nn refers to the slot number (ex. 01…05):

FunctionRegisterAccess
X0-X15 Digital InputsXnn000-015 (XWnn00)Read Only
Y0-Y13 Digital OutputsYnn000-013 (YWnn00)Read/Write
High-speed Counter OptionHSC Channel 1HSC Channel 2 
HSC Input PinX0X2Read Only
Quadrature InputsPair 1Pair 2 
Counter InputsX0, X1X2, X3Read Only
HSC Configuration RegisterMWnn00MWnn06Read/Write
HSC Counter Register (Current Value)MWnn01MWnn07Read/Write
HSC Preset RegisterMWnn03MWnn09Read/Write
HSC Enable BitMnn080Mnn176Read/Write
HSC Reset BitMnn081Mnn177Read/Write
Output FlagY2Y3 
PWM OutputsChannel 1 
OutputY0 Read Only
PWM Configuration RegisterMWnn24 Read/Write
Frequency Setting RegisterMWnn25 Read/Write
ON Duty Setting Register (Duty Cycle)MWnn27 Read/Write
Pulse Enable FlagMnn576 Read/Write
ON Duty Setting Error FlagMnn466 Read Only
Frequency Setting Error FlagMnn467 Read Only

Reference the table below when configuring each HSC Configuration Register:

Input ModeOutput ModeRegister Value
Normal InputN/A0
High Speed, Single Phase, Up/Down CounterOutput ON when preset is reached2
Output ON when counter is enabled,
OFF when preset is reached
258
Quadrature 4XOutput ON when preset is reached131
Output ON when counter is enabled,
OFF when preset is reached
387

Reference the table below when configuring the PWM Configuration Registers:

Output ModeRegister Value
Normal PWM (fixed frequency)1
Normal PWM (variable frequency)2
CW/CCW (fixed frequency)3
CW/CCW (variable frequency)4
Pulse/Direction (fixed frequency)7
Pulse/Direction (variable frequency)8
Trapezoidal (Fixed Pulse Mode)9

Wiring

Digital Inputs

HMC3-M1614Y-V2 Digital Input Wiring Diagram

Digital Outputs

HMC3-M1614Y-V2 Digital Output Wiring Diagram

HSC Single Phase Up Counter

HSC Single Phase Up Counter Wiring Diagram

HSC Single Phase Down Counter

HSC Single Phase Down Counter Wiring Diagram

HSC Quadrature

HSC Quadrature Counter

HMC3-M1616P V2

This module is a digital input/output module for the HMC2000 and HMC4000 Series models. It has 16 digital inputs.

The module also features 16 digital sourcing (PNP) outputs, 1 of which can be used for PWM operation.

[Note: HMC3 I/O Module V2 Series are only compatible with HMC2000/ HMC4000 Series Base Model]

16 Digital Inputs (2 high-speed pairs up to 200kHz)

16 Digital Outputs (1 PWM up to 1kHz)

HMC3-M1616P V2 I/O Module
Specifications
               Power12 VDC from base
               CertificationsCE, UL
Digital Inputs16 bidirectional inputs (2 high-speed pairs)
               Rated Input Voltage24 VDC +/- 15%
               Rated input currentUp to 5mA (per contact)
               Input impedance4.9K ohms
               Minimum ON voltage15 VDC
               Maximum OFF voltage5 VDC
               Turn ON Time10 mSec
               Turn OFF Time10 mSec
               IsolationOptically isolated from internal circuit
Digital Outputs16 sourcing outputs (PNP-type), 1 PWM
               Maximum PWM Output Frequency1KHz
               Minimum ON Output Voltage22 VDC
               Maximum ON Output Voltage30 VDC
               Minimum OFF Output Voltage0.2 VDC
               Maximum OFF Output Voltage1 VDC
               Rated Load250mA @ 24VDC
               Nominal load96 Ohms 6W (resistive) @ 24VDC
6VA (inductive, UPF)
High-speed Channels 
               No. of inputs2 channel pairs (X0/X1 and X2/X3)
               Maximum Input Frequency200 KHz
               Maximum Input Count4,294,967,295 (32-bit)
General 
               Connection methodRemovable terminals (3.81 mm pitch)
               Operating Temperature0 to 55°C
               Operating Humidity10% to 90% (non-condensing)
               Mechanical Dimension (W x H x D)1.88 x 4.25 x 1.61 inches [48x108x41mm]

Configuration

Use MAPware-7000 to assign input (X and XW), output (Y and YW) and configuration (M and MW) memory addresses to the module. These addresses are created according to the slot location of the module, where nn refers to the slot number (ex. 01…05):

FunctionRegisterAccess
X0-X15 Digital InputsXnn000-015 (XWnn00)Read Only
Y0-Y15 Digital OutputsYnn000-015 (YWnn00)Read/Write
High-speed Counter OptionHSC Channel 1HSC Channel 2 
HSC Input PinX0X2Read Only
Quadrature InputsPair 1Pair 2 
Counter InputsX0, X1X2, X3Read Only
HSC Configuration RegisterMWnn00MWnn06Read/Write
HSC Counter Register (Current Value)MWnn01MWnn07Read/Write
HSC Preset RegisterMWnn03MWnn09Read/Write
HSC Enable BitMnn080Mnn176Read/Write
HSC Reset BitMnn081Mnn177Read/Write
Output FlagY2Y3 
PWM OutputsChannel 1 
OutputY0 Read Only
PWM Configuration RegisterMWnn24 Read/Write
Frequency Setting RegisterMWnn25 Read/Write
ON Duty Setting Register (Duty Cycle)MWnn27 Read/Write
Pulse Enable FlagMnn576 Read/Write
ON Duty Setting Error FlagMnn466 Read Only
Frequency Setting Error FlagMnn467 Read Only

Reference the table below when configuring each HSC Configuration Register:

Input ModeOutput ModeRegister Value
Normal InputN/A0
High Speed, Single Phase, Up/Down CounterOutput ON when preset is reached2
Output ON when counter is enabled,
OFF when preset is reached
258
Quadrature 4XOutput ON when preset is reached131
Output ON when counter is enabled,
OFF when preset is reached
387

Reference the table below when configuring the PWM Configuration Registers:

Output ModeRegister Value
Normal PWM (fixed frequency)1
Normal PWM (variable frequency)2
CW/CCW (fixed frequency)3
CW/CCW (variable frequency)4
Pulse/Direction (fixed frequency)7
Pulse/Direction (variable frequency)8
Trapezoidal (Fixed Pulse Mode)9

Wiring

Digital Inputs

HMC3-M1616P-V2 Digital Input Wiring Diagram

Digital Outputs

HMC3-M1616P-V2 Digital Output Wiring Diagram

HSC Single Phase Up Counter

HSC Single Phase Up Counter Wiring Diagram

HSC Single Phase Down Counter

HSC Single Phase Down Counter Wiring Diagram

HSC Quadrature

HSC Quadrature Counter