Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with XINJE XD Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: XINJE XD Series
Website: http://www.xinje.com
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | XINJE XD Series | ||
| PLC I/F | RS232 | ||
| Baud rate | 19200 | ||
| Data bits | 8 | ||
| Parity | Even | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 | 0-255 |
NOTE: Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.
NOTE: During pass-through, HMI will stop communication with PLC.
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | M | DDDDD | 0 ~ 20479 | |
| B | X | OO | 0 ~ 77 | |
| B | Y | OO | 0 ~ 77 | |
| B | S | DDDD | 0 ~ 7999 | |
| B | SM | DDDD | 0 ~ 4095 | |
| B | T | DDDD | 0 ~ 4095 | |
| B | C | DDDD | 0 ~ 4095 | |
| B | ET | DD | 0 ~ 39 | |
| B | SEM | DDD | 0 ~ 127 | |
| B | HM | DDDD | 0 ~ 6143 | |
| B | HS | DDD | 0 ~ 999 | |
| B | HT | DDDD | 0 ~ 1023 | |
| B | HC | DDDD | 0 ~ 1023 | |
| B | HSC | DD | 0 ~ 39 | |
| B | X_Extension | OOOOO | 10000 ~ 11777 | |
| B | X_BD | OOOOO | 20000 ~ 20100 | |
| B | Y_Extension | OOOOO | 10000 ~ 11777 | |
| B | Y_BD | OOOOO | 20000 ~ 20100 | |
| W | D | DDDDD | 0 ~ 20479 | |
| W | ID | DD | 0 ~ 99 | |
| W | QD | DD | 0 ~ 99 | |
| W | SD | DDDD | 0 ~ 4095 | |
| W | TD | DDDD | 0 ~ 4095 | |
| W | CD | DDDD | 0 ~ 4095 | |
| W | ETD | DD | 0 ~ 39 | |
| W | HD | DDDD | 0 ~ 6143 | |
| W | HSD | DDDD | 0 ~ 1023 | |
| W | HTD | DDDD | 0 ~ 1023 | |
| W | HCD | DDDD | 0 ~ 1023 | |
| W | HSCD | DD | 0 ~ 39 | |
| W | FD | DDDD | 0 ~ 8191 | |
| W | SFD | DDDD | 0 ~ 5999 | |
| W | FS | DD | 0 ~ 47 | |
| W | ID_Extension | DDDDD | 10000 ~ 11599 | |
| W | ID_BD | DDDDD | 20000 ~ 20099 | |
| W | QD_Extension | DDDDD | 10000 ~ 11599 | |
| W | QD_BD | DDDDD | 20000 ~ 20099 |
NOTE: This driver uses the modbus protocol. Because of the mapping address, it cannot support the complete PLC address range.
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 8P Mini-DIN Male |
|
| Rx | ↔ (bidirectional) | 5 TX |
| Tx | ↔ (bidirectional) | 4 RX |
| GND | ↔ (bidirectional) | 8 GND |