Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with XINJE XC Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: XINJE XC Series
Website: www.xinje.com
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | XINJE XC Series | ||
| PLC I/F | RS232 | RS232 | |
| Baud rate | 19200 | ||
| Data bits | 8 | ||
| Parity | Even | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 | 0–255 |
NOTE: Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.
NOTE: During pass-through, HMI will stop communication with PLC.
Device Address
| Bit/Word | Device Type | Format | Range | Memo |
|---|---|---|---|---|
| B | M | DDDD | 0 ~ 8511 | |
| B | X | OOOO | 0 ~ 1037 | |
| B | Y | OOOO | 0 ~ 1037 | |
| B | S | DDDD | 0 ~ 1023 | |
| B | T | DDD | 0 ~ 618 | |
| B | C | DDD | 0 ~ 634 | |
| W | D | DDDD | 0 ~ 8511 | |
| W | TD | DDD | 0 ~ 618 | |
| W | CD | DDD | 0 ~ 634 | |
| W | FD_1 | DDDD | 0 ~ 5000 | |
| W | FD_2 | DDDD | 8000 ~ 8511 | |
| W | FD8000 | DDDD | 8000 ~ 8511 | |
| W | ID | DDDD | 0 ~ 1099 | |
| W | QD | DDDD | 0 ~ 1099 | |
| W | FS | DD | 0 ~ 15 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 8P Mini-DIN Male |
|
| Rx | ↔ (bidirectional) | 5 TX |
| Tx | ↔ (bidirectional) | 4 RX |
| GND | ↔ (bidirectional) | 8 GND |