Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Yaskawa Electric MP Series SIO (Extension) PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: YASKAWA MP2200, MP2300, MP2300S, MP9xx communication module.
Website: http://www.yaskawa.com/
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | YASKAWA MP Series SIO (Extension) | ||
| PLC I/F | RS485 | RS232/RS485 2w/4w | |
| Baud rate | 19200 | 9600~57600 | |
| Data bits | 8 | ||
| Parity | Even | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 | 1-31 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | SB | DDDDh | 0 ~ 8191F | |
| B | IB | HHHHh | 0 ~ FFFFF | |
| B | OB | HHHHh | 0 ~ FFFFF | |
| B | MB | DDDDDh | 0 ~ 65534F | |
| W | SW | DDDD | 0 ~ 8191 | |
| W | IW | HHHH | 0 ~ FFFF | |
| W | OW | HHHH | 0 ~ FFFF | |
| W | MW | DDDDD | 0 ~ 65534 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
Diagram 1: RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 9P 9D-Sub Male | |
| Rx | ↔ (bidirectional) | 2 TX |
| Tx | ↔ (bidirectional) | 3 RX |
| GND | ↔ (bidirectional) | 7 GND |
Diagram 2: RS-485 2W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | 217IF-01 RS485 14P Connector | |
| Data- | ↔ (bidirectional) | 2, 4 D- |
| Data+ | ↔ (bidirectional) | 1, 3 D+ |
| GND | ↔ (bidirectional) | 14 GND |