The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Yaskawa Electric MP Series — Memobus. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: YASKAWA MP2200, MP2300, MP2300S, MP9xx communication mudule

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeYASKAWA MP Series – Memobus
PLC I/FRS485/EthernetRS232/RS485 2w/4w, Ethernet
Baud rate192009600~57600
Data bits8
ParityEven
Stop bits1
Port no.502defaultEthernet Module Only
PLC sta. no.11-31

PLC Settings

SettingValue
Communication modeMEMOBUS, Slave, RTU

PLC Ethernet Setup

  1. Open Module Configuration

    Use MPE720 program software, open Module Configuration, then double-click 218IFA.
    MPE720 Engineering Manager showing Module Configuration with MP2300S CPU and slot assignments including MECHATROLINK module.
  2. Enter Transmission Parameters

    In Transmission Parameters, enter the MP2300S IP address, Subnet Mask, and Gateway IP. In Connection Parameter, set CNO-1 as follows: Local Port = 502, Node IP Address = 000.000.000.000, Node Port = 00000, Connect Type = TCP, Protocol Type = MEMOBUS, Code = RTU.
    MPE720 Transmission Parameters dialog showing IP address fields and Connection Parameter table with CNO-1 configured for TCP MEMOBUS RTU on local port 502.
  3. Configure MECHATROLINK as Master

    Click MECHATROLINK to set up the MP2300S PLC as Master.
    MPE720 MECHATROLINK dialog with Master/Slave set to Master, showing communication type MECHATROLINK-II CS Byte Mode and communication cycle settings.
  4. Save Configuration

    Close all dialogs and save the configuration to the MP2300S.

NOTE: Only CNO 01 can auto-communicate with one HMI. Other CNO connections require a ladder program created for communication.

NOTE: DIP SW2-2 of MP2300S must be set to the OFF position during normal communication. If set to ON, the IP address will be erased after a power reset and communication with the HMI will fail.

Device Address

Bit/WordDevice TypeFormatRangeMemo
BMB_1DDDDh0 ~ 9999fMB 0 ~ 9999
BMB_2DDDDDh100000 ~ 65534fMB 10000 ~ 65535
BIBHHHHH0 ~ a7ff0Read only
BIW_BitHHHHdd0 ~ a7ff15
WIWHHHH0 ~ a7ffRead only
DWILHHHH0 ~ a7ffRead only
DW (F)IFHHHH0 ~ a7ffRead only
WMWDDDDD0 ~ 65534Holding register
DWMLDDDDD0 ~ 65533Double word
DW (F)MFDDDDD0 ~ 65533Floating point

NOTE: When connecting via Ethernet interface, the maximum range of IW, IL, and IF is restricted.

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMIDirectionPLC
Pin assignmentsRS232
9P D-Sub
Male
Rx↔ (bidirectional)2 TX
Tx↔ (bidirectional)3 RX
GND↔ (bidirectional)7 GND

Diagram 2: RS-485 2W

HMIDirectionPLC
Pin assignments217IF-01 RS485
14P Connector
Data-↔ (bidirectional)2, 4 D-
Data+↔ (bidirectional)1, 3 D+
GND↔ (bidirectional)14 GND

Diagram 3: RS-485 4W

HMIDirectionPLC
Pin assignments217IF-01 RS422
14P Connector
Rx-↔ (bidirectional)2 TXD-
RX+↔ (bidirectional)1 TXD+
Tx-↔ (bidirectional)4 RXD-
Tx+↔ (bidirectional)3 RXD+
GND↔ (bidirectional)14 GND

Diagram 4: Ethernet

Use a standard straight-through (patch) Ethernet cable.

Straight-through Ethernet cable wiring diagram showing all 8 wire pairs — W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, Brown — connected pin-to-pin on both ends.