Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Yaskawa Electric CCMEP. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: YASKAWA CCMEP-100/ CCMEP-200
Website: yaskawa-control.co.jp
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | YASKAWA CCMEP | ||
| PLC I/F | RS485 4W | ||
| Baud rate | 38400 | ||
| Data bits | 8 | ||
| Parity | Even | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | 4_Bit | DDDDDdd | 100 ~ 6553515 | |
| W | 4 | DDDDD | 1 ~ 65535 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-485 4W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 4W 8P RJ45 Male | |
| Rx- | ↔ (bidirectional) | 4 TXD- |
| RX+ | ↔ (bidirectional) | 3 TXD+ |
| Tx- | ↔ (bidirectional) | 2 RXD- |
| Tx+ | ↔ (bidirectional) | 1 RXD+ |
| GND | ↔ (bidirectional) | 8 GND |