The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with GE Intelligent Platforms CMM. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

HMI Settings

Parameters Recommended Options Notes
PLC type GE CMM
PLC I/F RS232 RS232/RS485
Baud rate 19200 9600, 19200, 38400, 57600, 115200
Data bits 8 7, 8 Must set to 8 for this protocol
Parity Odd Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 0 0–0–255 Does not apply to this protocol

PLC Settings

Refer to the related PLC manual.

Device Address

Bit/Word Device type Format Range Memo
B I DDDDD 1 ~ 10000 Input relay
B Q DDDDD 1 ~ 10000 Output relay
B M DDDDD 1 ~ 10000 Auxiliary relay
B G DDDD 1 ~ 7680
B T DDD 1 ~ 256
B SA DDD 1 ~ 128
B SB DDD 1 ~ 128
B SC DDD 1 ~ 128
B S DDD 1 ~ 128
W AI DDDDD 1 ~ 10000 Analog input register
W AQ DDDDD 1 ~ 10000 Analog output register
W R DDDDD 1 ~ 32640 Data register

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-485 4W

HMI Direction PLC
Pin assignments RS485 4W
25P D-Sub Male
Rx- ↔ (bidirectional) 9
RX+ ↔ (bidirectional) 21
Tx- ↔ (bidirectional) 7
Tx+ ↔ (bidirectional) 13
GND ↔ (bidirectional) 25
↕︎ (tie) 24
↕︎ (tie) 10
11
↕︎ (tie) 22
23

Diagram 2: RS-232

HMI Direction PLC
Pin assignments RS232
25P D-Sub Male
Rx ↔ (bidirectional) 2
Tx ↔ (bidirectional) 3
GND ↔ (bidirectional) 7
↕︎ (tie) 4
5