The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with GE Intelligent Platforms SNP-X. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: GE 90-30, 90 micro and VersaMax series PLC, 90-70 series with

Website: ge.com

HMI Settings

Parameters Recommended Options Notes
PLC type GE SNP-X
PLC I/F RS485 4W RS232/RS485
Baud rate 19200 9600 ~ 115200
Data bits 8 7, 8 Must set to 8 for this protocol
Parity Odd Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 0 0–255 Does not apply to this protocol

PLC Setting

Refer to the related PLC manual.

Device Address

Bit/Word Device Format Range Memo
B I DDDDD 1 ~ 10000 Input relay
B Q DDDDD 1 ~ 10000 Output relay
B M DDDDD 1 ~ 10000 Auxiliary relay
B G DDDD 1 ~ 7680
B T DDD 1 ~ 256
B SA DDD 1 ~ 128
B SB DDD 1 ~ 128
B SC DDD 1 ~ 128
B S DDD 1 ~ 128
B R_bit DDDDDdd 100 ~ 3264015 Data register bit
W AI DDDDD 1 ~ 10000 Analog input register
W AQ DDDDD 1 ~ 10000 Analog output register
W R DDDDD 1 ~ 32640 Data register

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-485 4W (CPU Port: 90-30/VersaMax)

HMI Direction PLC
Pin assignments RS422
15P D-Sub
Male
Rx- ↔ (bidirectional) 12
RX+ ↔ (bidirectional) 13
Tx- ↔ (bidirectional) 7
Tx+ ↔ (bidirectional) 10
GND ↔ (bidirectional) 11
9
↕︎ (tie) 6
15
↕︎ (tie) 8
14

Diagram 2: RS-232 (CPU Port: 90-30 series CPU351/352/363/364)

HMI Direction PLC
Pin assignments RS232
6P RJ11
Male
Rx ↔ (bidirectional) 2
Tx ↔ (bidirectional) 5
GND ↔ (bidirectional) 3

Diagram 3: RS-232 (CPU Port: VersaMax series CPU001/002/005/E05)

HMI Direction PLC
Pin assignments RS232
8P RJ45
Male
Rx ↔ (bidirectional) 4
Tx ↔ (bidirectional) 3
GND ↔ (bidirectional) 8