The leader in industrial automation and control solutions

Introduction

All Maple Systems HMI Touch Screens programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with GE Intelligent Platforms SNP-X. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: GE 90-30, 90 micro and VersaMax series PLC, 90-70 series with

Website: www.ge.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeGE SNP-X
PLC I/FRS485 4WRS232/RS485
Baud rate192009600 ~ 115200
Data bits87, 8Must set to 8 for this protocol
ParityOddEven, Odd, None
Stop bits11, 2
PLC sta. no.00–255Does not apply to this protocol

PLC Setting

Refer to the related PLC manual.

Device Address

Bit/WordDeviceFormatRangeMemo
BIDDDDD1 ~ 10000Input relay
BQDDDDD1 ~ 10000Output relay
BMDDDDD1 ~ 10000Auxiliary relay
BGDDDD1 ~ 7680
BTDDD1 ~ 256
BSADDD1 ~ 128
BSBDDD1 ~ 128
BSCDDD1 ~ 128
BSDDD1 ~ 128
BR_bitDDDDDdd100 ~ 3264015Data register bit
WAIDDDDD1 ~ 10000Analog input register
WAQDDDDD1 ~ 10000Analog output register
WRDDDDD1 ~ 32640Data register

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-485 4W (CPU Port: 90-30/VersaMax)

HMIDirectionPLC
Pin assignmentsRS422
15P D-Sub
Male
Rx-↔ (bidirectional)12
RX+↔ (bidirectional)13
Tx-↔ (bidirectional)7
Tx+↔ (bidirectional)10
GND↔ (bidirectional)11
9
↕︎ (tie)6
15
↕︎ (tie)8
14

Diagram 2: RS-232 (CPU Port: 90-30 series CPU351/352/363/364)

HMIDirectionPLC
Pin assignmentsRS232
6P RJ11
Male
Rx↔ (bidirectional)2
Tx↔ (bidirectional)5
GND↔ (bidirectional)3

Diagram 3: RS-232 (CPU Port: VersaMax series CPU001/002/005/E05)

HMIDirectionPLC
Pin assignmentsRS232
8P RJ45
Male
Rx↔ (bidirectional)4
Tx↔ (bidirectional)3
GND↔ (bidirectional)8