The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Delta Electronics DVP Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: DELTA DVP series

Website: www.deltadriver.com

HMI Settings

ParameterRecommendedOptions
PLC typeDELTA DVP
PLC I/FRS232RS232, RS485
Baud rate96009600, 19200
Data bits77, 8
ParityEvenEven, Odd, None
Stop bits11
PLC sta. no.10–255

Support communications between HMI and PLC in pass-through mode.

Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.

PLC Settings

DVP-SS2 RS485 baud rate 19200 or higher must set D1038 (Data Response Delay Time).

D1038: Setting value range 0–20 (time unit: 0.1 ms)

Device Address

Bit/WordDevice TypeFormatRangeMemo
BXOOOOO0–23417 (octal)Input
BYOOOOO0–23417 (octal)Output
BMDDDDD0–65536Auxiliary Relay
BSDDDD0–9999Step Relay
BTDDDD0–9999Timer
BCDDDD0–9999Counter
BTV_BitDDDDdd0–999915Timer
WTVDDDD0–9999Timer
WCVDDD0–199Counter
WCV2DDD200–255Double Word Counter
WDDDDDD0–11999Data Register

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232 (8P Mini-DIN)

The following is the view from the soldering point of a connector.

8-pin DIN circular connector pinout for Delta DVP series serial programming port, pins numbered 1 through 8.
HMIDirectionPLC
Pin assignmentsRS232
8P Mini-DIN
Male
Rx↔ (bidirectional)5 TX
Tx↔ (bidirectional)4 RX
GND↔ (bidirectional)3/8 GND

Diagram 2: RS-485 2W

The following is the view from the soldering point of a connector.

3-wire RS-485 terminal block connection showing + (A), SG (signal ground), and − (B) terminals.
HMIDirectionPLC
Pin assignmentsRS485 2W Port
Data−↔ (bidirectional)2 Data−
Data+↔ (bidirectional)1 Data+
GND↔ (bidirectional)3 GND