Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Delta Electronics AH500. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: DELTA AH500
Website: http://www.deltadriver.com
HMI Setting
| Parameters | Recommended | Notes |
|---|---|---|
| PLC type | DELTA | |
| PLC I/F | RS232 | |
| Baud rate | 9600 | |
| Data bits | 7 | |
| Parity | Even | |
| Stop bits | 1 | |
| PLC sta. no. | 1 |
Device Address
| Bit/Word | Device Type | Format | Range | Memo |
|---|---|---|---|---|
| B | X | DDDdd | 0 ~ 51115 | |
| B | Y | DDDdd | 0 ~ 51115 | |
| B | S | DDDD | 0 ~ 2047 | |
| B | M | DDDD | 0 ~ 8191 | |
| B | SM | DDDD | 0 ~ 2047 | |
| B | T | DDDD | 0 ~ 2047 | |
| B | C | DDDD | 0 ~ 2047 | |
| B | HC | DD | 0 ~ 63 | |
| W | XW | DDD | 0 ~ 511 | |
| W | YW | DDD | 0 ~ 511 | |
| W | SW | DDDD | 0 ~ 2047 | |
| W | D | DDDDD | 0 ~ 32767 | |
| W | TV | DDDD | 0 ~ 2047 | |
| W | CV | DDDD | 0 ~ 2047 | |
| W | HCV | DD | 0 ~ 63 | |
| W | E | DD | 0 ~ 31 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
Diagram 1: RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 9P D-SUB | |
| Rx | ↔ (bidirectional) | 3 TX |
| Tx | ↔ (bidirectional) | 2 RX |
| GND | ↔ (bidirectional) | 5 GND |
Diagram 2: RS-485 2W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 2W 9P D-SUB | |
| Data- | ↔ (bidirectional) | 6 Data- |
| Data+ | ↔ (bidirectional) | 1 Data+ |
| GND | ↔ (bidirectional) | 5 GND |
Diagram 3: RS-485 4W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 4W 9P D-SUB | |
| Rx- | ↔ (bidirectional) | 9 TX- |
| RX+ | ↔ (bidirectional) | 4 TX+ |
| Tx- | ↔ (bidirectional) | 6 RX- |
| Tx+ | ↔ (bidirectional) | 1 RX+ |
| GND | ↔ (bidirectional) | 5 GND |