The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Delta Electronics AH500. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: DELTA AH500

Website: http://www.deltadriver.com

HMI Setting

ParametersRecommendedNotes
PLC typeDELTA
PLC I/FRS232
Baud rate9600
Data bits7
ParityEven
Stop bits1
PLC sta. no.1

Device Address

Bit/WordDevice TypeFormatRangeMemo
BXDDDdd0 ~ 51115
BYDDDdd0 ~ 51115
BSDDDD0 ~ 2047
BMDDDD0 ~ 8191
BSMDDDD0 ~ 2047
BTDDDD0 ~ 2047
BCDDDD0 ~ 2047
BHCDD0 ~ 63
WXWDDD0 ~ 511
WYWDDD0 ~ 511
WSWDDDD0 ~ 2047
WDDDDDD0 ~ 32767
WTVDDDD0 ~ 2047
WCVDDDD0 ~ 2047
WHCVDD0 ~ 63
WEDD0 ~ 31

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMIDirectionPLC
Pin assignmentsRS232
9P D-SUB
Rx↔ (bidirectional)3 TX
Tx↔ (bidirectional)2 RX
GND↔ (bidirectional)5 GND

Diagram 2: RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W
9P D-SUB
Data-↔ (bidirectional)6 Data-
Data+↔ (bidirectional)1 Data+
GND↔ (bidirectional)5 GND

Diagram 3: RS-485 4W

HMIDirectionPLC
Pin assignmentsRS485 4W
9P D-SUB
Rx-↔ (bidirectional)9 TX-
RX+↔ (bidirectional)4 TX+
Tx-↔ (bidirectional)6 RX-
Tx+↔ (bidirectional)1 RX+
GND↔ (bidirectional)5 GND