The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Cimon CM1-SC02A. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Cimon CM series, SC02A module

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeCimon CM1-SC02A
PLC I/FRS232
Baud rate384009600 ~ 115200
Data bits87,8
ParityNoneNone,Even,Odd
Stop bits11,2
PLC sta. no.10 ~ 254
  • Support communications between HMI and PLC in pass-through mode
  • Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode
  • When the pass-through function is executed due to protocol conflict, the communication between HMI and PLC will be interrupted

Device Address

Bit/WordDevice typeFormatRangeMemo
BXDDDDh0 ~ 1023f0-1F Read Only
BYDDDDh0 ~ 1023f0-F Read Only
BMDDDh0 ~ 999f
BKDDDh0 ~ 999f
BLDDDh0 ~ 999f
BFDDDh0 ~ 127fRead Only
BD_BitDDDDDh0 ~ 31999f
BTDDDh0 ~ 102f
BT_DecDDDD0 ~ 4095
BCDDDh0 ~ 102f
BC_DecDDDD0 ~ 4095
WDDDDDD0 ~ 31999
WSDD0 ~ 99Max. Range: 99
WTSDDDD0 ~ 4095
WTCDDDD0 ~ 4095
WCSDDDD0 ~ 4095
WCCDDDD0 ~ 4095
WZDDDD0 ~ 1023

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232 (CM1-SC02A: 9P D-Sub)

HMIDirectionPLC
Pin assignmentsRS232
9P D-Sub
Male
Rx↔ (bidirectional)3 TX
Tx↔ (bidirectional)2 RX
GND↔ (bidirectional)5 GND