The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Bosch Rexroth SIS (Absolute Addressing). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: IndraDrive HCS02

HMI Setting

Parameters Recommended Options Notes
PLC type Bosch Rexroth SIS (Absolute Addressing)
PLC I/F RS232
Baud rate 38400
Data bits 8
Parity None
Stop bits 1

Device Address

Bit/Word Device type Format Range Memo
B IX DDDDDdd 0 ~ 6553515
B QX DDDDDdd 0 ~ 6553515
B MX DDDDDdd 0 ~ 6553515
Byte IB DDDDD 0 ~ 65535
Byte QB DDDDD 0 ~ 65535
Byte MB DDDDD 0 ~ 65535
W IW DDDDD 0 ~ 65535
W QW DDDDD 0 ~ 65535
W MW DDDDD 0 ~ 65535
DW ID DDDDD 0 ~ 65535
DW QD DDDDD 0 ~ 65535
DW MD DDDDD 0 ~ 65535

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232 (CM1-SC02A: RS-232 9P D-Sub)

HMI Direction PLC
Pin assignments RS232
9P D-Sub
Male
Rx ↔ (bidirectional) 3 TX
Tx ↔ (bidirectional) 2 RX
GND ↔ (bidirectional) 5 GND