Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with SAIA PCD PGU Mode. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: SAIA PCD series PGU mode

Website: http://www.saia-burgess.com/

HMI Settings

Parameters Recommended Options Notes
PLC type SAIA PCD PGU Mode PDS driver
PLC I/F RS232 RS232, RS485
Baud rate 9600 9600, 19200
Data bits 7 7, 8
Parity Even Even, Odd, None
Stop bits 1 1
PLC sta. no. 1 0-255

Device Address

Bit/Word Device type Format Range Memo
B Flag DDDD 0 ~ 8191
B Output DDD 0 ~ 511
B Input DDD 0 ~ 511
W Register DDDD 0 ~ 4095
W Counter DDDD 0 ~ 1599
W Timer DDDD 0 ~ 1599
W Reg_Float DDDD 0 ~ 4095 support single float point
W Reg_Word DDDD 0 ~ 4095

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMI Direction PLC
Pin assignments RS232 9P
D-Sub Male
Rx ↔ (bidirectional) 3
Tx ↔ (bidirectional) 2
GND ↔ (bidirectional) 5
RTS ↔ (bidirectional) 6
↕︎ (tie) 7
8
66 DSR (Of PGU Port): PGU connected.