The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Parker Hannifin SLVD Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Parker SLVD Servo, SLVD1N, SLVD2N, SLVD5N, SLVD7N,

HMI Settings

Parameters Recommended Options Notes
PLC type Parker SLVD Series
PLC I/F RS485 4W
Baud rate 9600 9600/19200
Data bits 8 7, 8
Parity Even Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 0 0–31
Online simulator YES

Device Address

Bit/Word Device type Format Range Memo
B Par_Binary DDDDdd 0 ~ 999915 Set bit parameter
W Par_One_Word DDDD 0 ~ 9999 Set 2 bytes parameter
DW Par_Two_Word DDDD 0 ~ 9999 Set 4 bytes parameter
W Par_One_Byte DDDD 0 ~ 9999 Set 1 byte parameter
W RESET D 0
W RUN D 0

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 4W

HMI Direction PLC
Pin assignments RS485 4W
15P D-Sub
Male
Rx- ↔ (bidirectional) 7 TX-
RX+ ↔ (bidirectional) 12 TX+
Tx- ↔ (bidirectional) 2 RX-
Tx+ ↔ (bidirectional) 1 RX+
↕︎ (tie) 6 TER
GND ↔ (bidirectional) 3 GND