Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Parker Hannifin Compumotor 6K Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Parker Compumotor 6K Series | ||
| PLC I/F | RS232 | ||
| Baud rate | 9600 | ||
| Data bits | 8 | ||
| Parity | None | ||
| Stop bits | 1 | ||
| PLC sta. no. | 0 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | VARB(L) | DDDdd | 1 ~ 125 | The lower 16 bits data of VARB |
| B | VARB(H) | DDDdd | 1 ~ 125 | The higher 16 bits data of VARB |
| D | RUN_PRG | D | 0 | |
| DW | VARI | DDD | 1 ~ 125 | |
| DW | VAR | DDD | 1 ~ 125 | Must select single float data |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 9P D-Sub Male | |
| Rx | ↔ (bidirectional) | 3 TX |
| Tx | ↔ (bidirectional) | 2 RX |
| GND | ↔ (bidirectional) | 5 GND |