Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Danfoss VLT2800 Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: VLT2800 series

Website: http://www.danfoss.com/

HMI Setting

Parameters Recommended Options Notes
PLC type Danfoss VLT2800 Series
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 1 0-126 According to PLC

PLC Setting

Parameter Value
Communication mode 9600, Even, 8, 1 (default)

Device Address

Bit/Word Device type Format Range Memo
DW Parameter DDDD 0 ~ 2000 Set Parameter
W Reference D 0 ~ 1 Control Bus Reference

The control word register is set according to the station number. If the station number is 1, the control word will be RW100 and RW101; if the station number is 2, the control word will be RW102 and RW103, and so on.

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W
Terminal
Data-↔ (bidirectional)69 Data-
Data+↔ (bidirectional)68 Data+
GND↔ (bidirectional)