All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Danfoss FC Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: FC051, FC100, FC200, FC300, VLT Micro Driver

Website: http://www.danfoss.com/

HMI Setting

Parameters Recommended Options Notes
PLC type Danfoss FC Series
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 1

Device Address

Para_Index 310.1=31001, Para_Index310.0=31000

Bit/Word Device type Format Range Memo
DW Parameter DDDD 0 ~ 9999 Set Parameter
W Reference D 0 ~ 1 Control Bus Reference
DW Para_Index DDDDDD 0 ~ 999999 Set Parameter(Index)
W Parameter_text DDDD 0 ~ 9999
W Para_Index_test DDDDDD 0 ~ 999999

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 2W

HMIDirectionPLC
Pin assignmentsFC RS485 2W
Terminal
Data-↔ (bidirectional)69 Data-
Data+↔ (bidirectional)68 Data+
GND↔ (bidirectional)
  • *RW100 set PCD1 Control Word of station 1
  • *RW101 read PCD1 Status Word of station 1
  • *RW102 set PCD1 Control Word of station 2
  • *RW103 read PCD1 Status Word of station 2
  • *RW104 set PCD1 Control Word of station 3
  • *RW105 read PCD1 Status Word of station 3
  • *RW106 set PCD1 Control Word of station 4
  • *RW107 read PCD1 Status Word of station 4