The leader in industrial automation and control solutions

Introduction

All Maple Systems HMI Screens programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Danfoss FC Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: FC051, FC100, FC200, FC300, VLT Micro Driver

Website: www.danfoss.com

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeDanfoss FC Series
PLC I/FRS485 2W
Baud rate9600
Data bits8
ParityEven
Stop bits1
PLC sta. no.1

Device Address

Para_Index 310.1=31001, Para_Index310.0=31000

Bit/WordDevice typeFormatRangeMemo
DWParameterDDDD0 ~ 9999Set Parameter
WReferenceD0 ~ 1Control Bus Reference
DWPara_IndexDDDDDD0 ~ 999999Set Parameter(Index)
WParameter_textDDDD0 ~ 9999
WPara_Index_testDDDDDD0 ~ 999999

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 2W

HMIDirectionPLC
Pin assignmentsFC RS485 2W
Terminal
Data-↔ (bidirectional)69 Data-
Data+↔ (bidirectional)68 Data+
GND↔ (bidirectional)
  • *RW100 set PCD1 Control Word of station 1
  • *RW101 read PCD1 Status Word of station 1
  • *RW102 set PCD1 Control Word of station 2
  • *RW103 read PCD1 Status Word of station 2
  • *RW104 set PCD1 Control Word of station 3
  • *RW105 read PCD1 Status Word of station 3
  • *RW106 set PCD1 Control Word of station 4
  • *RW107 read PCD1 Status Word of station 4