Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with SEW MOVITRAC LTE. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | SEW MOVITRAC LTE | ||
| PLC I/F | RS-485 2W | ||
| Baud rate | 115200 | ||
| Data bits | 8 | ||
| Parity | None | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 | ||
| Online simulator | YES | ||
| Extend address mode | NO |
Device Addresses
| Bit/Word | Device Type | Format | Range | Memo |
|---|---|---|---|---|
| W | P-1 | D | 0 ~ 1 | Max. speed limit |
| W | P-2 | D | 0 ~ 1 | Min. speed limit |
| W | P-3 | D | 0 ~ 1 | Acceleration ramp time |
| W | P-4 | D | 0 ~ 1 | Deceleration ramp time |
| W | P-5 | D | 0 ~ 1 | Stop mode select |
| W | P-6 | D | 0 ~ 1 | Energy optimizer |
| W | P-7 | D | 0 ~ 1 | Motor rated voltage |
| W | P-8 | D | 0 ~ 1 | Motor rated current |
| W | P-9 | D | 0 ~ 1 | Motor rated frequency |
| W | P-10 | D | 0 ~ 1 | Motor rated speed |
| W | P-11 | D | 0 ~ 1 | Voltage boost |
| W | P-12 | D | 0 ~ 1 | Terminal / Keypad control |
| W | P-13 | D | 0 ~ 1 | Trip log |
| W | P-14 | D | 0 ~ 1 | Extended menu access code |
| W | P-15 | D | 0 ~ 1 | Digital input function set |
| W | P-16 | D | 0 ~ 1 | Analog input V / mA |
| W | P-17 | D | 0 ~ 1 | Output switching frequency |
| W | P-18 | D | 0 ~ 1 | User relay output select |
| W | P-19 | D | 0 ~ 1 | User relay output limit |
| W | P-20 | D | 0 ~ 1 | Preset speed 1 |
| W | P-21 | D | 0 ~ 1 | Preset speed 2 |
| W | P-22 | D | 0 ~ 1 | Preset speed 3 |
| W | P-23 | D | 0 ~ 1 | Preset speed 4 |
| W | P-24 | D | 0 ~ 1 | Deceleration ramp time 2 |
| W | P-25 | D | 0 ~ 1 | Analog output function select |
| W | P-26 | D | 0 ~ 1 | Skip frequency hysteris band |
| W | P-27 | D | 0 ~ 1 | Skip frequency |
| W | P-28 | D | 0 ~ 1 | V/F characteristic adjustment voltage |
| W | P-29 | D | 0 ~ 1 | V/F characteristic adjustment frequency |
| W | P-30 | D | 0 ~ 1 | Terminal mode restart function |
| W | P-31 | D | 0 ~ 1 | Keypad mode restart function |
| W | P-32 | D | 0 ~ 1 | DC injection enable / duration |
| W | P-33 | D | 0 ~ 1 | Spin start |
| W | P-34 | D | 0 ~ 1 | Brake chopper enable |
| W | P-35 | D | 0 ~ 1 | Analog input scaling factor |
| W | P-36 | D | 0 ~ 1 | Comms address; SBus enable/baudrate select; Trip enable / delay |
| W | P-37 | D | 0 ~ 1 | Access code definition |
| W | P-38 | D | 0 ~ 1 | Parameter access lock |
| W | P-39 | D | 0 ~ 1 | Analog input off-set |
| W | P-40 | D | 0 ~ 1 | Display speed scaling factor |
| W | P-00-01 | D | 0 ~ 1 | Analog input 1 value |
| W | P-00-02 | D | 0 ~ 1 | Analog input 2 value |
| W | P-00-03 | D | 0 ~ 1 | Speed reference input |
| W | P-00-04 | D | 0 ~ 1 | Digital input status |
| W | P-00-05 | D | 0 ~ 1 | Reserved |
| W | P-00-06 | D | 0 ~ 1 | Reserved |
| W | P-00-07 | D | 0 ~ 1 | Applied motor voltage |
| W | P-00-08 | D | 0 ~ 1 | DC bus voltage log |
| W | P-00-09 | D | 0 ~ 1 | Heatsink temperature |
| W | P-00-10 | D | 0 ~ 1 | Hours run meter |
| W | P-00-11 | D | 0 ~ 1 | Run time since last trip (1) |
| W | P-00-12 | D | 0 ~ 1 | Run time since last trip (2) |
| W | P-00-13 | D | 0 ~ 1 | Run time since last disable |
| W | P-00-14 | D | 0 ~ 1 | Reserved |
| W | P-00-15 | D | 0 ~ 1 | DC bus voltage log |
| W | P-00-16 | D | 0 ~ 1 | Thermistor temperature log |
| W | P-00-17 | D | 0 ~ 1 | Motor current |
| W | P-00-18 | D | 0 ~ 1 | Software ID, IO and motor control |
| W | P-00-19 | D | 0 ~ 1 | Drive serial number |
| W | P-00-20 | D | 0 ~ 1 | Drive identifier |
NOTE: P-00-01 through P-00-20 are read only.
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-485 2W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 2W 8P RJ45 Male | |
| Data- | ↔ (bidirectional) | 4- |
| Data+ | ↔ (bidirectional) | 5+ |
| GND | ↔ (bidirectional) | GND |