The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Schneider Electric IMS Motion. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Schneider MDrivePlus

Website: motion.schneider-electric.com

HMI Settings

Parameters Recommended Options Notes
PLC typeSchneider IMS MOTION
PLC I/FRS232
Baud rate9600
Data bits8
ParityEven
Stop bits1
PLC sta. no.0

Device Address

Bit/Word Device type Format Range Memo
WAD0
WC1D0
WCD0
WDD0
WPD0
WR1D0
WR2D0
WR3D0
WR4D0
WVID0
WVMD0
WEXD0
WSD0
WMRD0
WD1D0
WD2D0
WD3D0
WD4D0
WDED0
WDGD0
WHCD0
WHTD0
WMSD0
WMTD0
WPYD0
WQDD0
WRCD0
WWTD0
WBDD0
WRam_KD0
WRam_GD0
WRam_QD0

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMI Direction PLC
Pin assignmentsRS232
9P D-Sub
Female
Rx↔ (bidirectional)3
Tx↔ (bidirectional)2
GND↔ (bidirectional)5