All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Schneider Electric Modbus TCP/IP. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Schneider Modbus RTU TCP/IP Device. (M221)

Website: schneider-electric.com

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeSchneider MODBUS TCP/IP
PLC I/FEthernet
Port no.502
PLC sta. no.10~255

PLC Setting

SettingValue
Ethernet frame formatEthernet II format

Device Address

Bit/WordDevice TypeFormatRangeMemo
B%IXDDDDo0 ~ 81927Input bit (read only)
B%QXDDDDo0 ~ 81927Write multiple coils
B%MXDDDDDDo0 ~ 1310707Output register bit (octal)
B%MDDDDD0 ~ 65535Output bit
B%MW_BitDDDDDdd0 ~ 6553515Output register bit (decimal)
B1xDDDDD0 ~ 65535Input bit (read only)
B0x_single_BitDDDDD0 ~ 65535
B0x_multi_coilsDDDDD0 ~ 65535Write multiple coils
B3x_BitDDDDDdd0 ~ 6553515Input register bit (read only)
B%IDDDddd0 ~ 255255
B%QDDDddd0 ~ 255255
B%SDDDDD0 ~ 65535
B%XDDD0 ~ 200
W%MWDDDDD0 ~ 65535Output register
DW%MDDDDDD0 ~ 32767Output register
W3xDDDDD0 ~ 65535Input Register (read only)
DW5xDDDDD0 ~ 655354x double word swap
DW6xDDDDD0 ~ 655354x single word write
DW4x_DoubleDDDDD0 ~ 65535
DW%IWDDD.DDD0 ~ 255.255
DW%QWDDD.DDD0 ~ 255.255
DW%SWDDDDD0 ~ 65535
DW%KWDDDD0 ~ 65535
DW%IWSDDD.DDD0 ~ 255.255
DW%QWSDDD.DDD0 ~ 255.255
DW%TM_VDDD0 ~ 254
DW%TM_PDDD0 ~ 254
DW%TM_QDDD0 ~ 254

NOTE: PLC model TM221CE40R does not support %MX, %IX, or %QX addresses.

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Ethernet straight-through cable wiring diagram showing eight color-coded wire pairs connected pin-to-pin: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, Brown.