All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with an Omron E5CN/E5EZ/E5ZN. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: OMRON E5CN series temperature controller with communication options. E5EN/CN/GN/EZ/ZN series.

Website: http://oeiweb.omron.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeOMRON E5CN
PLC I/FRS485 2W
Baud rate96009600/19200/38400/57600/115200
Data bits77, 8
ParityEvenEven, Odd, None
Stop bits21, 2
PLC sta. no.00–99
Online simulatorYES
Broadcast commandYES
Extend address modeYES

*Support communications between HMI and PLC in pass-through mode.

*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.

Device Address

Bit/WordDeviceFormatRangeMemo
BStatus_CH1DD0–31Page 40
BStatus_CH2DD0–31
BC0_BitHHHHdd0–270f31
BC1_BitHHHHdd0–270f31
BC2_BitHHHHdd0–270f31
BC3_BitHHHHdd0–270f31
DWC0HHHH0–270fRead only (Hex) Page 34
DWC1HHHH0–270fRead/Write (Hex) Page 35
DWC2HHHH0–270fRead/Write (Hex) Page 35
DWC3HHHH0–270fRead/Write (Hex) Page 36
WCode00_00H0Communications writing OFF
WCode00_01H0Communications writing
WCode01_00H0Run
WCode01_01H0Stop
WCode02_00H0Multi-SP Set point 0
WCode02_01H0Multi-SP Set point 1
WCode02_02H0Multi-SP Set point 2
WCode02_03H0Multi-SP Set point 3
WCode03_00H0AT cancel
WCode03_01H0AT execute
WCode04_00H0Write mode (Backup)
WCode04_01H0Write mode (RAM)
WCode05_00H0Save RAM data
WCode06_00H0Software reset
WCode07_00H0Move to setup area 1
WCode08_00H0Move to protect level
WCode01_10H0
WCode01_11H0
WCode01_F0H0
WCode01_F1H0
WCode02_10H0
WCode02_11H0
WCode02_F0H0
WCode02_F1H0
WCode03_10H0
WCode03_11H0
WCode03_F0H0
WCode03_F1H0
WCode09_00H0
WCode09_01H0
WCode09_10H0
WCode09_11H0
WCode09_F0H0
WCode09_F1H0
WCode0A_00H0
WCode0B_00H0
WCode0C_00H0
WCode0C_01H0
WCode0C_02H0
WCode0C_0FH0
WCode0C_10H0
WCode0C_11H0
WCode0C_12H0
WCode0C_1FH0
WCode0C_F0H0
WCode0C_F1H0
WCode0C_F2H0
WCode0C_FFH0

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 2W

HMIDirectionPLC
Pin assignmentsOMRON E5CN
Terminal
Data−↔ (bidirectional)12 B
Data+↔ (bidirectional)11 A
GND↔ (bidirectional)GND

NOTE: For communication with OMRON E5EZ, please set communication settings to 9600, E, 7, 2, station no. 1.