Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric XGI Cnet. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: LS XGT series XGI CPU series with communication module XGL-CH2A

Website: www.lgis.com

HMI Settings

Parameters Recommended Options Notes
PLC typeLS XGI Cnet
PLC I/FRS232RS232/RS485 4W
Baud rate1152009600~115200
Data bits87, 8
ParityNoneEven, Odd, None
Stop bits11
PLC sta. no.00~32

Device Address

Bit/Word Device type Format Range Memo
BAW_BitDDDDDDh0 ~ 262143f
BIW_BitDDD.DD.Dh0 ~ 127.15.3f
BQW_BitDDD.DD.Dh0 ~ 127.15.3f
BMW_BitDDDDDDh0 ~ 262143f
BRW_BitDDDDDh0 ~ 32767f
BWW_BitDDDDDDh0 ~ 524287f
BFW_BitDDDDh0 ~ 4095f
BKW_BitDDDDh0 ~ 8399f
BLW_BitDDDDDh0 ~ 11263f
BNW_BitDDDDDh0 ~ 25087f
BUW_BitDD.DD.DDh0 ~ 31.15.31f
BAXDDDDDDD0 ~ 4194303
BIXDDD.DD.DD0 ~ 127.15.63
BQXDDD.DD.DD0 ~ 127.15.63
BMXDDDDDDD0 ~ 4194303
BRXDDDDDD0 ~ 524287
BWXDDDDDDD0 ~ 8388607
BFXDDDDD0 ~ 65535
BKXDDDDDD0 ~ 134399
BLXDDDDDDD0 ~ 1880223
BNXDDDDDD0 ~ 401407
BUXDD.DD.DDD0 ~ 31.15.511
WAWDDDDDD0 ~ 262143
WIWDDD.DD.D0 ~ 127.15.3
WQWDDD.DD.D0 ~ 127.15.3
WMWDDDDDD0 ~ 262143
WRWDDDDD0 ~ 32767
WWWDDDDDD0 ~ 524287
WFWDDDD0 ~ 4095
WKWDDDD0 ~ 8399
WLWDDDDD0 ~ 11263
WNWDDDDD0 ~ 25087
WUWDD.DD.DD0 ~ 31.15.31
DWMDDDDDDD0 ~ 131071
ByteMBDDDDDDD0 ~ 2097151
LWMLDDDDDD0 ~ 262143

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMI Direction PLC
Pin assignmentsXGL-CH2A CH1
RS232 9P D-Sub Male
Rx↔ (bidirectional)3
Tx↔ (bidirectional)2
GND↔ (bidirectional)5

Diagram 2: RS-485 4W

HMI Direction PLC
Pin assignmentsXGL-CH2A CH2
5P Terminal
Rx-↔ (bidirectional)TXD-
RX+↔ (bidirectional)TXD+
Tx-↔ (bidirectional)RXD-
Tx+↔ (bidirectional)RXD+
GND↔ (bidirectional)GND