Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric XEC/XGI CPU Direct. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: LS XEC/XGI CPU RS232 port
Website: http://www.lgis.com/
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | LS XEC/XGI CPU DIRECT | ||
| PLC I/F | RS232 | RS232 | |
| Baud rate | 115200 | 9600~115200 | |
| Data bits | 8 | 7, 8 | |
| Parity | None | Even, Odd, None | |
| Stop bits | 1 | 1 | |
| PLC sta. no. | 1 | 1 |
- Supports communications between HMI and PLC in pass-through mode.
- Set
LW-9903to2to enhance the speed of download/upload PLC program in pass-through mode.
Device Address
| Bit/Word | Device Type | Format | Range |
|---|---|---|---|
| B | AW_Bit | DDDDDDh | 0 ~ 262143f |
| B | IW_Bit | DDD.DD.Dh | 0 ~ 127.15.3f |
| B | QW_Bit | DDD.DD.Dh | 0 ~ 127.15.3f |
| B | MW_Bit | DDDDDDDh | 0 ~ 1048575f |
| B | RW_Bit | DDDDDh | 0 ~ 32767f |
| B | WW_Bit | DDDDDDh | 0 ~ 524287f |
| B | FW_Bit | DDDDh | 0 ~ 4095f |
| B | KW_Bit | DDDDh | 0 ~ 8399f |
| B | LW_Bit | DDDDDh | 0 ~ 11263f |
| B | NW_Bit | DDDDDh | 0 ~ 25087f |
| B | UW_Bit | DD.DD.DDh | 0 ~ 31.15.31f |
| B | AX | DDDDDDD | 0 ~ 4194303 |
| B | IX | DDD.DD.DD | 0 ~ 127.15.63 |
| B | QX | DDD.DD.DD | 0 ~ 127.15.63 |
| B | MX | DDDDDDDD | 0 ~ 16777199 |
| B | RX | DDDDDD | 0 ~ 524287 |
| B | WX | DDDDDDD | 0 ~ 8388607 |
| B | FX | DDDDDD | 0 ~ 134399 |
| B | KX | DDDDDD | 0 ~ 134399 |
| B | LX | DDDDDDD | 0 ~ 1880223 |
| B | NX | DDDDDD | 0 ~ 401407 |
| B | UX | DD.DD.DDD | 0 ~ 31.15.511 |
| W | AW | DDDDDD | 0 ~ 262143 |
| W | IW | DDD.DD.D | 0 ~ 127.15.3 |
| W | QW | DDD.DD.D | 0 ~ 127.15.3 |
| W | MW | DDDDDDD | 0 ~ 1048575 |
| W | RW | DDDDD | 0 ~ 32767 |
| W | WW | DDDDDD | 0 ~ 524287 |
| W | FW | DDDD | 0 ~ 4095 |
| W | KW | DDDD | 0 ~ 8399 |
| W | LW | DDDDD | 0 ~ 11263 |
| W | NW | DDDDD | 0 ~ 25087 |
| W | UW | DD.DD.DD | 0 ~ 31.15.31 |
| DW | MD | DDDDDD | 0 ~ 524287 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | XGI CPU RS232 9P D-Sub Male | |
| Rx | ↔ (bidirectional) | 3 |
| Tx | ↔ (bidirectional) | 2 |
| GND | ↔ (bidirectional) | 5 |