The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric XEC Cnet. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: LS XGB Series XEC CPU with communication module XGL-CH2A

Website: http://www.lgis.com/

HMI Settings

Parameters Recommended Options Notes
PLC typeLS XEC Cnet
PLC I/FRS232RS232/RS485
Baud rate1152009600 ~ 115200
Data bits87, 8
ParityNoneEven, Odd, None
Stop bits11, 2
PLC sta. no.00 ~ 32

Device Addresses

Bit/Word Device Type Format Range Memo
BAW_BitDDDDDDh0 ~ 262143fAutomatic variable bit
BIW_BitDDD.DD.Dh0 ~ 127.15.3fInput device bit
BQW_BitDDD.DD.Dh0 ~ 127.15.3fOutput device bit
BMW_BitDDDDDDDh0 ~ 1048575fDirect variable bit
BRW_BitDDDDDh0 ~ 32767fDirect variable bit
BWW_BitDDDDDh0 ~ 65535fDirect variable bit
BFW_BitDDDDh0 ~ 2047fSystem flag bit
BKW_BitDDDDh0 ~ 8399fBuilt-in special flag bit
BLW_BitDDDDDh0 ~ 11263fHigh speed link flag bit
BNW_BitDDDDDh0 ~ 25087fP2P flag bit
BUW_BitDD.DD.DDh0 ~ 31.15.31fAnalog flag bit
BAXDDDDDDD0 ~ 4194303
BIXDDD.DD.DD0 ~ 127.15.63
BQXDDD.DD.DD0 ~ 127.15.63
BMXDDDDDDDD0 ~ 16777199
BRXDDDDDD0 ~ 524287
BWXDDDDDDD0 ~ 1048575
BFXDDDDD0 ~ 32767
BKXDDDDDD0 ~ 134399
BLXDDDDDDD0 ~ 1880223
BNXDDDDDD0 ~ 401407
BUXDD.DD.DDD0 ~ 31.15.511
WAWDDDDDD0 ~ 262143Automatic variable
WIWDDD.DD.D0 ~ 127.15.3Input device
WQWDDD.DD.D0 ~ 127.15.3Output device
WMWDDDDDDD0 ~ 1048575Direct variable
WRWDDDDD0 ~ 32767Direct variable
WWWDDDDD0 ~ 65535Direct variable
WFWDDDD0 ~ 2047System flag
WKWDDDD0 ~ 8399Built-in special flag
WLWDDDDD0 ~ 11263High speed link flag
WNWDDDDD0 ~ 25087P2P flag
WUWDD.DD.DD0 ~ 31.15.31Analog flag
DWMDDDDDDD0 ~ 524287
ByteMBDDDDDDD0 ~ 2097151
LWMLDDDDDD0 ~ 262143

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

RS232

HMIDirectionPLC
Pin assignmentsRS232 Terminal
Rx↔ (bidirectional)Tx
Tx↔ (bidirectional)Rx
GND↔ (bidirectional)SG

RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W Terminal
Data-↔ (bidirectional)485-
Data+↔ (bidirectional)485+
GND↔ (bidirectional)GND