Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric MASTER-K10S1. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: LS MASTER-K10S1
Website: http://www.lgis.com/
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | LS MASTER-K10S1 | ||
| PLC I/F | RS232 | RS232/RS485 | |
| Baud rate | 9600 | ||
| Data bits | 8 | 8 | |
| Parity | None | None | |
| Stop bits | 1 | 1 | |
| PLC sta. no. | 0 |
Device Address
| Bit/Word | Device | Format | Range | Memo |
|---|---|---|---|---|
| B | PW_Bit | DDDh | 0 ~ 255f | I/O Relay (P) |
| B | KW_Bit | DDDh | 0 ~ 255f | Keep Relay (K) |
| B | MW_Bit | DDDh | 0 ~ 255f | Auxiliary Relay (M) |
| B | LW_Bit | DDDh | 0 ~ 255f | Link Relay (L) |
| B | FW_Bit | DDDh | 0 ~ 255f | Special Relay (F) |
| B | TX | DDD | 0 ~ 255 | Timer (T) |
| B | CX | DDD | 0 ~ 255 | Counter (C) |
| W | TW | DDD | 0 ~ 255 | Timer Present Value |
| W | CW | DDD | 0 ~ 255 | Counter Present Value |
| W | DW | DDDD | 0 ~ 9999 | Data Register (D) |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 9P D-Sub Male |
|
| Rx | ↔ (bidirectional) | 3 |
| Tx | ↔ (bidirectional) | 2 |
| GND | ↔ (bidirectional) | 5 |