The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric MASTER-K10S1. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: LS MASTER-K10S1

Website: http://www.lgis.com/

HMI Settings

Parameters Recommended Options Notes
PLC typeLS MASTER-K10S1
PLC I/FRS232RS232/RS485
Baud rate9600
Data bits88
ParityNoneNone
Stop bits11
PLC sta. no.0

Device Address

Bit/Word Device Format Range Memo
BPW_BitDDDh0 ~ 255fI/O Relay (P)
BKW_BitDDDh0 ~ 255fKeep Relay (K)
BMW_BitDDDh0 ~ 255fAuxiliary Relay (M)
BLW_BitDDDh0 ~ 255fLink Relay (L)
BFW_BitDDDh0 ~ 255fSpecial Relay (F)
BTXDDD0 ~ 255Timer (T)
BCXDDD0 ~ 255Counter (C)
WTWDDD0 ~ 255Timer Present Value
WCWDDD0 ~ 255Counter Present Value
WDWDDDD0 ~ 9999Data Register (D)

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

HMIDirectionPLC
Pin assignments RS232
9P D-Sub
Male
Rx↔ (bidirectional)3
Tx↔ (bidirectional)2
GND↔ (bidirectional)5