All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric MASTER-K Modbus RTU. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: LS MASTER-K MODBUS RTU

Website: http://www.lgis.com/

HMI Setting

Parameters Recommended Options Notes
PLC type LS MASTER-K MODBUS RTU
PLC I/F RS485 2W
Baud rate 9600
Data bits 8 8
Parity Even Even
Stop bits 1 1
PLC sta. no. 1

Device Address

Bit/Word Device Format Range Memo
B PW_Bit DDDDh 0 ~ 9999f I/O Relay (P)
B KW_Bit DDDDh 0 ~ 9999f Keep Relay (K)
B MW_Bit DDDDh 0 ~ 9999f Auxiliary Relay (M)
B LW_Bit DDDDh 0 ~ 9999f Link Relay (L)
B FW_Bit DDDDh 0 ~ 9999f Special Relay (F)
B DW_Bit DDDDh 0 ~ 9999f
W MW DDDD 0 ~ 9999
W LW DDDD 0 ~ 9999
W FW DDDD 0 ~ 9999
W TW DDDD 0 ~ 9999 Timer (T)
W CW DDDD 0 ~ 9999 Counter (C)
W SW DDDD 0 ~ 9999
W DW DDDD 0 ~ 9999 Data Register (D)
DW TD DDDD 0 ~ 9999
DW CD DDDD 0 ~ 9999
DW SD DDDD 0 ~ 9999
DW DD DDDD 0 ~ 9999

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMI Direction PLC
Pin assignments RS232 9P D-Sub Male
Rx ↔ (bidirectional) 3
Tx ↔ (bidirectional) 2
GND ↔ (bidirectional) 5