Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric MASTER-K CPU Direct. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: LS MASTER-K series: K80S, K120S, K200S, K300S, K1000S, K7M

Website: http://www.lgis.com/

HMI Settings

Parameters Recommended Options Notes
PLC typeLG MASTER-K CPU Direct
PLC I/FRS232RS232/RS485
Baud rate384009600, 19200, 38400
Data bits88
ParityNoneEven, Odd, None
Stop bits11
PLC sta. no.00–31

NOTE: Supports communications between HMI and PLC in pass-through mode. Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.

Online simulator: YES

Device Address

Bit/Word Device type Format Range Memo
BPW_BitDDDh0 ~ 255fI/O Relay (P)
BKW_BitDDDh0 ~ 319fKeep Relay (K)
BMW_BitDDDDh0 ~ 1919fAuxiliary Relay (M)
BLW_BitDDDh0 ~ 639fLink Relay (L)
BFW_BitDDDh0 ~ 319fSpecial Relay (F)
BTXDDD0 ~ 255
BCXDDD0 ~ 255
BSXDD.DD0 ~ 99.99
BDW_bitDDDDh0 ~ 9999fD_bit
WMWDDDD0 ~ 1919Word type for M
WLWDDD0 ~ 639Word type for L
WFWDDD0 ~ 319Word type for F
WPWDDD0 ~ 159
WKWDDD0 ~ 319
WTWDDD0 ~ 255Timer Present Value
WCWDDD0 ~ 255Counter Present Value
WDWDDDD0 ~ 9999Data Register (D)

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMIDirectionPLC
Pin assignmentsRS232 9P D-Sub Male
Rx↔ (bidirectional)3
Tx↔ (bidirectional)2
GND↔ (bidirectional)5