Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric MASTER-K Cnet. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: LS MASTER-K series: K80S, K200S, K300S, and K1000S
Website: http://www.lgis.com/
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | LS MASTER-K Cnet | ||
| PLC I/F | RS232 | RS232/RS485 | |
| Baud rate | 38400 | 9600, 19200, 38400 | |
| Data bits | 8 | 8 | |
| Parity | None | Even, Odd, None | |
| Stop bits | 1 | 1 | |
| PLC sta. no. | 0 | 0–31 | |
| Online simulator | YES |
Device Addresses
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | PW_Bit |
DDDh |
0 ~ 255f | I/O Relay (P) |
| B | KW_Bit |
DDDh |
0 ~ 255f | Keep Relay (K) |
| B | MW_Bit |
DDDh |
0 ~ 255f | Auxiliary Relay (M) |
| B | LW_Bit |
DDDh |
0 ~ 255f | Link Relay (L) |
| B | FW_Bit |
DDDh |
0 ~ 255f | Special Relay (F) |
| B | TX |
DDDh |
0 ~ 255 | |
| B | CX |
DDDh |
0 ~ 255 | |
| B | DW_bit |
DDDDh |
0 ~ 9999f | D_bit |
| B | SX |
DD.DD |
0 ~ 99.99 | |
| W | MW |
DDD |
0 ~ 255 | Word type for M |
| W | LW |
DDD |
0 ~ 255 | Word type for L |
| W | FW |
DDD |
0 ~ 255 | Word type for F |
| W | PW |
DD |
0 ~ 63 | |
| W | KW |
DD |
0 ~ 31 | |
| W | TW |
DDD |
0 ~ 255 | Timer Present Value |
| W | CW |
DDD |
0 ~ 255 | Counter Present Value |
| W | DW |
DDDD |
0 ~ 9999 | Data Register (D) |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-232 (CPU Port Cnet I/F)
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 9P D-Sub Male |
|
| Rx | ↔ (bidirectional) | 7 |
| Tx | ↔ (bidirectional) | 4 |
| GND | ↔ (bidirectional) | 5 |
NOTE: If connected with Cnet module, please refer to Cnet module document.