All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric GM3467 (LOADER). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: LS GLOFA series GM3, GM4, GM6, GM7 CPU port

HMI Settings

Parameters Recommended Options Notes
PLC typeLS GLOFA GM3467 (LOADER)
PLC I/FRS232
Baud rate38400
Data bits8
ParityNone
Stop bits1
PLC sta. no.1

Device Address

Bit/Word Device type Format Range Memo
BMXDDDDDD0 ~ 524272
BIXddDdd0 ~ 6376300.0.0 ~ 63.7.63 (dd.D.dd)
BQXddDdd0 ~ 6376300.0.0 ~ 63.7.63 (dd.D.dd)
WIWHHH0 ~ 273
WQWHHH0 ~ 273
WMWDDDDD0 ~ 32767
WMDDDDDD0 ~ 16383

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232 (LS GLOFA Series)

HMIDirectionPLC
Pin assignments RS232
9P D-Sub
Male
Rx↔ (bidirectional)3
Tx↔ (bidirectional)2
GND↔ (bidirectional)5