Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric GLOFA Cnet. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: LS GLOFA GM6/GM7 CPU port. G7L-CUEB / G6L-CUEB / G4L-CUEA / G3L-CUEA Cnet module

Website: http://www.lgis.com/

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeLS GLOFA Cnet
PLC I/FRS232RS232/RS485 2W/4W
Baud rate96009600~115200
Data bits87, 8
ParityNoneEven, Odd, None
Stop bits11
PLC sta. no.00~31

PLC Settings

SettingValue
Communication mode9600,N,8,1 (default), Cnet protocol
Communication moduleApplicable mode: 1 dedicated communication

Device Addresses

Bit/WordDevice typeFormatRangeMemo
BMXDDDDD0 ~ 32767Internal Relay
BIXddDdd0 ~ 63763Input
BQXddDdd0 ~ 63763Output
WMWDDDDD0 ~ 32767Data Register
DWMDDDDDD0 ~ 16383Double Word

IX and QX format: dd D dd

  • dd = Module Contact Number (0 to 63)
  • D = Slot Number (0 to 7)
  • dd = Base Number (0 to 63)

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232: 9P D-Sub to 9P D-Sub (CPU Port)

HMIDirectionPLC
Pin assignmentsRS232 9P D-Sub Male
Rx↔ (bidirectional)7
Tx↔ (bidirectional)4
GND↔ (bidirectional)5

Diagram 2: RS-232: Communication Module (G7L-CUEB / G6L-CUEB / G4L-CUEA / G3L-CUEA Cnet RS232)

HMIDirectionPLC
Pin assignmentsRS232 9P D-Sub Male
Rx↔ (bidirectional)3
Tx↔ (bidirectional)2
GND↔ (bidirectional)5
↕︎ (tie)1
7
8
↕︎ (tie)4
6

Diagram 3: RS-485 4W: Communication Module (G7L-CUEC / G6L-CUEC / G4L-CUEA / G3L-CUEA Cnet RS422)

HMIDirectionPLC
Pin assignmentsRS422 terminal
Rx-↔ (bidirectional)SDB
RX+↔ (bidirectional)SDA
Tx-↔ (bidirectional)RDB
Tx+↔ (bidirectional)RDA
GND↔ (bidirectional)GND