Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Koyo (Automation Direct) CLICK V3 Modbus TCP/IP PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: KOYO CLICK C0, C2 series
Website: automationdirect.com
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | KOYO CLICK V3 MODBUS TCP/IP | ||
| PLC I/F | Ethernet | ||
| Port no. | 502 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | X | Ddd | 1 ~ 816 | |
| B | Y | Ddd | 1 ~ 816 | |
| B | C | DDDD | 1 ~ 2000 | |
| B | T | DDD | 1 ~ 500 | |
| B | CT | DDD | 1 ~ 250 | |
| B | SC | DDDD | 1 ~ 1000 | |
| B | X0 | DD | 21 ~ 36 | X021-X036 |
| B | Y0 | DD | 21 ~ 36 | Y021-Y036 |
| B | X1 | DD | 21 ~ 36 | X121-X136 |
| B | Y1 | DD | 21 ~ 36 | Y121-Y136 |
| B | X2 | DD | 21 ~ 36 | X221-X236 |
| B | Y2 | DD | 21 ~ 36 | Y221-Y236 |
| B | X3 | DD | 21 ~ 36 | X321-X336 |
| B | Y3 | DD | 21 ~ 36 | Y321-Y336 |
| B | X4 | DD | 21 ~ 36 | X421-X436 |
| B | Y4 | DD | 21 ~ 36 | Y421-Y436 |
| B | X5 | DD | 21 ~ 36 | X521-X536 |
| B | Y5 | DD | 21 ~ 36 | Y521-Y536 |
| B | X6 | DD | 21 ~ 36 | X621-X636 |
| B | Y6 | DD | 21 ~ 36 | Y621-Y636 |
| B | X7 | DD | 21 ~ 36 | X721-X736 |
| B | Y7 | DD | 21 ~ 36 | Y721-Y736 |
| B | X8 | DD | 21 ~ 36 | X821-X836 |
| B | Y8 | DD | 21 ~ 36 | Y821-Y836 |
| W | DS | DDDD | 1 ~ 4500 | |
| DW | DD | DDDD | 1 ~ 1000 | |
| W | DH | DDD | 1 ~ 500 | |
| DW | DF | DDD | 1 ~ 500 | |
| W | XD | D | 0 ~ 8 | |
| W | YD | D | 0 ~ 8 | |
| W | TD | DDD | 1 ~ 500 | |
| DW | CTD | DDD | 1 ~ 250 | |
| W | SD | DDDD | 1 ~ 1000 | |
| W | TXT | DDDD | 1 ~ 1000 | |
| W | XDu | D | 0 ~ 8 | |
| W | YDu | D | 0 ~ 8 |
Wiring Diagram
The diagram below shows the Ethernet cable wiring.