All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Keyence KV-10/16/24/40/80/Visual KV Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: KEYENCE KV series, KV16~80

Website: www.keyence.com

HMI Settings

Parameter Recommended Options Notes
PLC Type KEYENCE KV-10/16/24/40/80/Visual KV Series
PLC I/F RS232 RS232
Baud Rate 9600
Data Bits 8
Parity Even
Stop Bits 1
PLC Sta. No. 0

Device Address

Bit/Word Device Type Format Range Memo
B RLY DDDdd0* 0 ~ 655150* dd: 0 ~ 15
B DM_Bit DDDDDh 0 ~ 65535f
W DM DDDDD 0 ~ 65535
W TM DDDD 0 ~ 8999
W T DDDD 0 ~ 9999
W T_Curr DDDD 0 ~ 9999 Timer_Current
W T_Preset DDDD 0 ~ 9999
W C DDDD 0 ~ 9999
W C_Curr DDDD 0 ~ 9999 Counter_Current
W C_Preset DDDD 0 ~ 9999

NOTE: If the Relay (bit) register is used, place a zero at the end of the address. For example, to read Relay (bit) 100, write the address as 1000.

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232 (CPU Port)

HMI Direction PLC
Pin assignments OP-26486
9P D-Sub
Male
Rx ↔ (bidirectional) 3
Tx ↔ (bidirectional) 2
GND ↔ (bidirectional) 5

Diagram 2: RS-232 (9P D-Sub to 6P RJ11)

Keyence KV series programming port RJ connector showing 6 pins numbered 1 through 6.
HMI Direction PLC
Pin assignments RS232
6P RJ11
Male
Rx ↔ (bidirectional) 2 SD
Tx ↔ (bidirectional) 4 RD
GND ↔ (bidirectional) 3 SG